Below, sample programs are shown for some frequently used control and regulation tasks.
They may help at programming.
Control from terminal between 5 and 60 Hz
Submenu
Setting
source of the control reference signal
terminal
terminal control
yes
60 Hz
5 Hz
frequency inhibit limit
70 Hz
control reference signal
5 - 60 Hz
digital input 1 type selection
N
digital input 2 type selection
N
The commands start, stop, direction and frequency change can be given from the terminal.
Control from terminal blocks with potentiometer between 10 and 50 Hz
At the lower extreme position of the potentiometer the driven unit has to stop.
Submenu
Setting
source of the control reference signal
analogue IN 1.
analogue input 1. type
potentiometer
analogue input 1. stop range
3%
analogue input 1. hysteresis
1%
50 Hz
10 Hz
frequency inhibit limit
55 Hz
The commands start, stop and direction, can be given through the digital terminal blocks (SD), the frequency can be
changed with the potentiometer connected to the analogue terminal blocks (SA).
T
he lower extreme position of the potentiometer sets “waiting” mode!
Control from terminal, reference signal change between 1 and 100 Hz with motor potentiometer
function
The motor potentiometer function should be activated from the Digital IN1 and IN2 inputs or from the terminal!
Submenu
Setting
source of the control reference signal
motor potentiometer
terminal control
yes
digital input 1 type selection
N
digital input 2 type selection
N
100 Hz
1 Hz
frequency inhibit limit
110 Hz
digital input 4 type selection
logical functions
logical functions
motor potentiometer up
digital input 5 type selection
logical functions
logical functions
motor potentiometer down
10,0 s
10,0 s
no
motor potentiometer
The commands start, stop and directions can be given from the terminal.
Changing the frequency can be effected with Digital IN 4. and IN 5. or in display mode with the terminal push buttons
and
(motor potentiometer up and down).
Summary of Contents for V3D Series