M-34-01-06 3/31/2016
14
DQ15D/T-DQ15D Manual
Configuration (Set-up)
1
To configure the DQ15D, press
and
simultaneously and hold for approximately 6
seconds. The screen displays
AC.0
.
2
While the
0
is flashing, use
to change this
to
11
. Press
SET
. The control will be in the
configuration mode. While in this mode, the
screen displays the values of various configu-
ration settings. The first setting to display is
the
U1
setting. See setting summary. By using
and
keys, it is possible to scroll through
the list of settings to those needing modifica-
tion.
Adjust Configuration Setting
1
To adjust a setting while in the Configuration
Mode, use
and
to bring the particular set-
ting into the view on the screen.
2
Press SET to change the value of the setting.
Once SET has been released, the display will
flash.
3
Use and to scroll through the options for
the selected setting.
4
After the option has been determined, press
SET
once more to lock the new value into
memory.
5
After completing all changes to the configura-
tion of the control, the new configuration must
be saved. To save the new value, press
and
simultaneously. This will cause the control to
store the new values internally and then reset
the unit.
Note: Switching off power to the unit before saving the new con-
figuration will cause all changes to be lost.
Sensor DIP Switch
When using the sensor 5416 or 5447 boards, an
on-board DIP switch must also be configured.
Sw
1
Sw
2
Sw
3
Type
OFF OFF OFF 1000 ohm RTD
ON
OFF OFF 100 ohm RTD
OFF ON
OFF voltage
OFF OFF ON
current
OFF OFF OFF frequency