M-34-01-06 3/31/2016 

 

 

           

DQ15D/T-DQ15D Manual

 

Voltage Signal Calibration

 

The  DQ15D  control  measures  DC  voltage  and 
compares that measurement with a  standard  set of 
values in the control memory.

 

 

 

Calibration  procedures  require  the  removal  of 
the rear cover of the control. It also requires that 
power  is ON, exposing the technician to poten-
tially  lethal  voltages.  Exercise  EXTREME  CARE 
and  wear  teste

d  electrician’s  gloves  whenever 

power is on. 

 

Les  procédures  de  calibration  nécessitent 
l'enlèvement  du  panneau  arrière  du  contrôle. 
Ça  exige  aussi  que  le  courant  électrique  est 
allumé  ce  qui  expose  le  technicien  à  des  ten-
sions  potentiellement  létales.  Utilisez  toujours 
un  soin  extrême  et  portez  des  gants  certifiés 
d'électricien quand le courrant est allumé.

 

 

Equipment Needed 

Optional  input  boards,  Item  #  5447  or  5416  need-
ed.

 

Verify Standard Values

 

To  restore,  update  or  merely  verify  that  this  standard 
set of  values is correct, do the following:

 

 

Make  sure  that  the  DIP  switch  settings  are  OFF, 
ON,  OFF.  See  Dip  Switch  Settings in 

Configura-

tion (Setup)

.

 

 

The  voltage  signal  must  be  connected  across 
terminals  #1  and  #2  of  the  Adder  Board  (Item  # 
5416 or  5447). Terminal#2 is common (negative), 
and terminal #1 is the signal connection (positive).

 

 

Always  observe  polarity.

 

 

 
 
 

 

Calibration Procedure

 

Turn OFF all power. 

Remove rear cover. 

Remove voltage input wiring. 

Install  a  voltage  calibrator  or  power  supply  to  ter-
minals 1 and 2. 

 

CAREFULLY  restore  power  to  the  controller,  en-
suring  that  you  do  not  come  in  contact  with  any 
exposed voltage. 

Press 

  and 

  simultaneously  and  hold  for  ap-

proximately  6  seconds.  The  screen  displays 

AC.0.While the 0 is flashing, use 

 to change this 

to  22.  Press  SET.  The  control  screen  displays 
CAL1. 

Adjust power supply to 1.0V. 

Press  and  hold  SET  for  one  second.  The  screen 
displays Hold. Wait for display to change to CAL2. 

Adjust calibrator to 10.0V. 

10 

Press  and  hold  SET  for  one  second.  The  screen 
displays Hold. Wait for display to reset and display 
10.0. 

11 

Turn  OFF  power  to  the  control  and  remove  the 
calibrator.  Reinstall  the  voltage  input  and  the  rear 
cover of the control. Return the calibrated control-
ler to service.

 

3-Wire RTD Calibration 

– Jumper Cable in 

Place for Second Resistor 

Summary of Contents for DQ15D

Page 1: ...fset U2 16 OutputSignalOffset U3 16 SignalFilterSetting U4 16 SetPoint1DeadBand U5 16 SetPoint2DeadBand U6 17 PowerSaveSetPointDeadBand U7 17 DisplayStabilizer U8 17 SetPointLimit L 17 SP2andU7Disable...

Page 2: ...Outputs SP1 Set Point reverse acting SPDT 20A resistive 240 VAC max 1HP 240 VAC max 1 2 HP 120VAC SP2 Set Point direct acting SPDT 2A resistive 240 VAC max 1 10HP 240 VAC max 1 20 HP 120VAC ON OFF Dif...

Page 3: ...ys de energize and the screen displays a flashing AAA The power save night setback feature permits the use of a second heating Set Point to conserve energy when required Installation Procedure DQ15D i...

Page 4: ...ill interrupt the heater power supply in the event of low solution level Process Technology heaters include a thermal device Protector 1 2 or 3 on the heater to monitor the heat er s surface temperatu...

Page 5: ...gram Set Points or tem perature limits When DQ15D reaches the Set Point it will energize one or both relays SP1 Heat Set Point for normal Heating Mode opera tion Controls SP1 relay SP2 Cool Set Point...

Page 6: ...he numeric P SET POINT value 4 To change the Set Point value press SET while the P SET POINT value displays value will flash 5 Once the value flashes press or to change the value 6 Press SET once to l...

Page 7: ...r and the fixed end of the other resistor to establish an input value of a single resistor i e 1000 ohms as shown Install the jumper cable between the loose end of one resistor and the fixed end of th...

Page 8: ...Two precision resistors tolerance 0 1 or bet ter with a fixed value equal to the RTD nominal value i e 1000 or 100 ohms A suitable jumper cable to facilitate changing input resistance A short piece of...

Page 9: ...reset After it resets the approximate temperature value for the connected precision resistors should display i e 511 F or 266 C 13 Turn OFF power to the controller and remove the precision resistors...

Page 10: ...settings are OFF ON OFF See Dip Switch Settings in Configura tion Setup The voltage signal must be connected across terminals 1 and 2 of the Adder Board Item 5416 or 5447 Terminal 2 is common negativ...

Page 11: ...rs un soin extr me et portez des gants certifi s d lectricien quand le courrant est allum Calibration Procedure 1 Turn OFF all power 2 Remove rear cover 3 Remove input leads 4 Install the 0 20 mA DC c...

Page 12: ...aussi que le courant lectrique est allum ce qui expose le technicien des ten sions potentiellement l tales Utilisez toujours un soin extr me et portez des gants certifi s d lectricien quand le courran...

Page 13: ...lso requires that power is ON exposing the technician to poten tially lethal voltages Exercise EXTREME CARE and wear tested electrician s gloves whenever power is on Les proc dures de calibration n ce...

Page 14: ...n of the letter c will define the exact nature of the problem c A small c in the upper left hand corner indicates the control is relying on default factory set calibra tion values This happens when th...

Page 15: ...set ting into the view on the screen 2 Press SET to change the value of the setting Once SET has been released the display will flash 3 Use and to scroll through the options for the selected setting...

Page 16: ...ing tells the DQ15D control what type of sensor it is using Value Board Sensor Type Sensor Description 1 5414 or 5416 2 wire RTD Platinum RTD TCR 0 00385 ohm ohm C 2 5414 or 5416 2 wire RTD Platinum R...

Page 17: ...sor and maintained in memory These samples are then averaged to provide an active filter of the signal Using a small value for this setting will cause the DE20 control to respond more quickly to sudde...

Page 18: ...Current Sensor Number represents hundredths of milliamps 0 01 mA Resistance Signal Devices Number represents ohms Frequency Signal Devices Setting represents hertz counts second If the Power Save SET...

Page 19: ...us or Fahrenheit is being displayed If the tem perature being measured is greater than 999 degrees the units are not shown because the display is limited to four positions F5 Temperature Units Convers...

Page 20: ...protection This can happen for example if arc or spot welding equipment is close to the control or if they share a common power line It can occur if flame ignition systems or electrostatic precipitato...

Reviews: