502 069 02
Manual
Power Monitor, PD 3260
37/79
Functions =
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Single-phase monitor
Three-phase monitor
Channel can be disabled
SWNo $AF: ChError.
ChError is a record of the following structure:
Record
His: Array[0..7] of Boolean;
(* Offset = 0 *)
Act: Array[0..7] of Boolean;
(* Offset = 2 *)
End;
The 8 bits in ChError.His and ChError.Act have the following meaning. When an error occurs,
the corresponding bit is set in both ChError.His and ChError.Act. When the error disappears, the
bit is cleared in ChError.Act.
ChError:
7 6 5 4 3 2 1 0
Module Error
CurrentHigh
VoltageHigh
HighAlarm (Power)
LowAlarm (Power)
Symmetry Error
External Error
Not used
Bit 7
Module error: If this bit is set, the rest of the bits have no meaning, because a Module
error can lead to random error codes on individual channels (also see "Service channel").