background image

The display range of temperature
The control range of temperature
Load rating
Display accuracy
Swing (cycle rate or differential)

Power source

Operating ambient
Operating humidity
Dimensions of thermostat

41ºF to 95ºF (5ºC to 35ºC)
44ºF to 90ºF (7ºC to 32ºC)
1 amp per terminal, 1.5 amp maximum all terminals combined
± 1ºF
Heating is adjustable from 0.4ºF to 2.0ºF 
Cooling is adjustable from 0.4ºF to 2.0ºF 
18 to 30 VAC, NEC Class II, 50/60 Hz for hardwire (common wire)
Battery power from 2 AA Alkaline Energizer batteries
32ºF to +105ºF (0º to +41ºC)
90% non-condensing maximum
4.7”W x 4.4”H x 1.1”D

13

SPECIFICATIONS & CONTACT INFORMATION

Specifications

Pro1 IAQ Inc.

1111 S. Glenstone

Suite 2-100

Springfield, MO 65804

Toll-free: 1-888-Pro1iaq (776-1427)

Toll Number (Outside the USA):  330-821-3600

Web: http://www.pro1iaq.com

Hours of Operation: Monday - Friday 9 AM - 6 PM Eastern

Summary of Contents for Toptech TT-S-855

Page 1: ...mmon Wire with Battery Backup Power Type 1 n o i t p i r c s e D Gas or Oil Heat Electric Furnace Heat Pump No Aux or Emergency Heat Heat Pump with Aux or Emergency Heat Multi stage Systems Heat Only Systems Heat Only Systems Cool Only Systems Millivolt Yes Yes Yes Yes Yes Yes Yes Yes Yes Rev 0950 Una versión española de este manual puede ser descargada en www pro1iaq com U S Registered Trademark ...

Page 2: ... are in direct sunlight With an outside wall behind the thermostat In areas that do not require conditioning Where there are dead spots or drafts in corners or behind doors Where there might be concealed chimneys or pipes Where appliances could radiate heat Pick an installation location that is easy for the user to access The temperature of the location should be representative of the building Wal...

Page 3: ...isplayed when thermostat program is permanently overridden 1 will appear in the display when second stage of heat or cool is on 2 will appear for third stage of heat System operation indicators The COOL HEAT or FAN icon will display when the COOL HEAT or FAN is on NOTE The compressor delay feature is active if these icons are flashing The compressor will not turn on until the 5 minute delay has el...

Page 4: ...oducts are mercury free However if the product you are replacing contains mercury dispose of it properly Your local waste management authority can give you instructions on recycling and proper disposal Horizontal mount Horizontal mount Vertical mount Vertical mount For vertical mount put one screw top and one screw bottom For horizontal mount put one screw left and one screw right C O B W E W2 R G...

Page 5: ...ergized in cooling Fan relay Emergency heat relay First stage of heat cool Second stage of cool second stage of heat Auxiliary heat relay third stage of heat This thermostat is shipped from the factory to operate a conventional heating and cooling system This thermostat will also operate a heat pump system See the heat pump configuration step on page 8 of this manual to configure the thermostat fo...

Page 6: ...s and a larger swing setting will cause fewer cycles Keypad lockout allows you to configure the thermostat so that none or some of the keys do not function The heating swing setting is adjustable from 0 4 F to 2 F For example A swing setting of 0 5 F will turn the heating on at approximately 0 5 F below the setpoint and turn the heating off at approximately 0 5 F above the setpoint Pick PA or FU P...

Page 7: ... or 24 Hour Clock Use the or key to turn on or off ON This feature turns your system on before the WAKE programming time to ensure the enviroment is at the WAKE setpoint when the WAKE time period begins This recovery changes over time based on the previous days experience Morning Recovery Use the or key to select 7d for 7 day 5d for 5 1 1 or 0d for nonprogammable 5d You can configure this thermost...

Page 8: ... one character to another See note below on operation If selected on you will see the input screen after pressing next step Note If Contractor Call Number is selected ON your phone number will show in the display if there has been a continuous call for heating or cooling for 24 hours or if the light button is held down for 3 seconds To remove the phone number from the display hold the light button...

Page 9: ...LLATION Mount Thermostat Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat then push gently until the thermostat snaps in place On the back of the thermostat insert 2 AA Alkaline batteries included ...

Page 10: ...ing Use the or key to select the current day of the week Press NEXT STEP The current hour is flashing Use the or key to select the current hour When using 12 hour time make sure the correct a m or p m choice is selected Press NEXT STEP Minutes are now flashing Use the or key to select current minutes Press DONE when completed 1 2 3 4 5 6 7 8 All programmable Pro1 thermostats are shipped with an en...

Page 11: ...time period Note If you want the fan to run continuously during this time period select ON with the FAN key Press NEXT STEP The setpoint temperature is flashing Use the or key to make your setpoint selection for the weekday WAKE period Press NEXT STEP Repeat steps 4 through 7 for weekday LEAVE time period for weekday RETURN time period and for weekday SLEEP time period Repeat steps 4 through 7 for...

Page 12: ...STEP Repeat steps 4 thru 7 for Monday LEAVE time period for Monday RETURN time period and for Monday SLEEP time period PROGRAMMING THE THERMOSTAT 12 1 2 3 4 5 6 7 8 Monday Repeat steps 4 thru 7 for the remaining days of the week Tuesday Wednesday Thursday Friday Saturday Sunday A Note About Auto Changeover Auto changeover will switch between heating and cooling as needed It is very important to ma...

Page 13: ...s adjustable from 0 4ºF to 2 0ºF Cooling is adjustable from 0 4ºF to 2 0ºF 18 to 30 VAC NEC Class II 50 60 Hz for hardwire common wire Battery power from 2 AA Alkaline Energizer batteries 32ºF to 105ºF 0º to 41ºC 90 non condensing maximum 4 7 W x 4 4 H x 1 1 D 13 SPECIFICATIONS CONTACT INFORMATION Specifications Pro1 IAQ Inc 1111 S Glenstone Suite 2 100 Springfield MO 65804 Toll free 1 888 Pro1iaq...

Reviews: