background image

• From the FG terminal at the rear side of GP unit, please take grounding exclu-

sively [within ground resistance of 100 W].

9

Precaution for Grounding

10

Precautions for Input/Output Signal Lines

• Input and Output signal lines must be separated from the power control cables for

operational circuits.

• If this is not possible, use a shielded cable and the shield should be grounded.

Connect the power cable following the steps below.

1. Check to make sure the Power is Off.

2. With a plus screwdriver, remove the cover on the Power Input Terminal Block.

3. Disconnect the screws from the 3 terminals to be used, align the wire rings and

re-insert the screws.

(Please make sure the connection of the wires are correct.)

The torque necessary for fastening the screws is between 0.5-0.6N

m.

Please pay special attention to the following instructions when connecting the
power cable to the GP unit.

• If the supply voltage exceeds the GP unit range, connect a voltage transformer.
• For between the line and ground, select a power supply that is low in noise.  If

there is an excess amount of noise, connect a noise reducing transformer.

• When supplying power to the GP unit, please separate the input/output and opera-

tion unit lines.

• To increase the noise quality, simply twist the power cable before connecting it

to the GP unit.

• The power supply cable must not be bundled or kept close to main circuit lines

(high voltage, high current), or input/output signal lines.

• Connect a surge absorber to deal with power surges.
• To reduce noise, make the power cable as short as possible.
• After turning this unit OFF, be sure to wait a few seconds before turning ON

again. If the unit is started within a few seconds, it may not start up correctly.

8

Precautions for Supplying Power

Summary of Contents for GP477R-EG41-24VP

Page 1: ...t or press the touch panel with too much force for it may cause irreparable damage Do not use GP in an environment where the surrounding temperature exceeds the specification range for it may damage t...

Page 2: ...earth terminal Be sure to connect this terminal in accordance with UL standards Installation and operation instructions are provided with each GP These installation instructions contain the following...

Page 3: ...g damaged or missing please contact your local GP distributor im mediately Package Contents Manual GP477R 577R Series User sManual Extra Cost Options Cables Adapters Screen editor software are optiona...

Page 4: ...d terminals for AC power cable E Auxiliary Input Output AUX Operates the Touch Switch System Alarm Buzzer Run outputs and Remote Reset inputs F Serial Interface RS 232C RS 422 Serial interface Connect...

Page 5: ...minal If necessary you may also need to connect the FG terminal to the other unit s FG terminal depending on the type of the other unit you use Pin Signal Name Condition Pin Signal Name Condition 1 FG...

Page 6: ...PDB2 5 PDB3 6 PDB4 7 PDB5 8 PDB6 9 PDB7 10 1 INIT 11 BUSY 12 NC 13 NC 14 GND When making a cable please be aware of the following For RS 422 Connection The following pairs of pin s must be connected...

Page 7: ...over XM2S 1511 madebyOMRONCorp JackScrew XM2Z 0071 madebyOMRONCorp Use rough metric type M2 6 x 0 45p threads used to hold the cable s set fastening screws in place 5 AUX Interface Input Output Pin Co...

Page 8: ...screws with too much force can cause a damage Panel GPunit 1 0 1 0 Before installing the GP into a cabinet or panel check that the Installa tion gasket is securely attached to the unit Confirm the Ins...

Page 9: ...inals with a sleeve 7 Wiring To avoid electric shock be sure the Power Cable is unplugged from the power outlet when connecting the cable to the GP unit GP477R EG41 24VP can only take DC24V input If y...

Page 10: ...N m Please pay special attention to the following instructions when connecting the power cable to the GP unit If the supply voltage exceeds the GP unit range connect a voltage transformer For between...

Reviews: