PS-4000B Series User Manual
64
Grounding
Overview
The grounding resistance between the PS-B unit’s Functional Ground (FG) and
Ground must be 100
or less. When using a long grounding wire, check the
resistance and if required replace a thin wire with a thicker wire and place it in a duct.
In addition, please refer to the table below for maximum line lengths for various wire
thicknesses.
Ground Wire Dimensions
Precaution
Dedicated Ground
Connect the Functional Ground (FG) to a dedicated ground.
Shared Ground Allowed
If a dedicated ground is not possible, use a shared ground, as shown.
Wire Thickness
Maximum Line Length
2.5 mm
2
(13 AWG)
30 m (98 ft.)
60 m (196 ft.) round trip.
WARNING
UNINTENDED EQUIPMENT OPERATION
Use only the authorized grounding configurations shown below.
Confirm that the grounding resistance is 100
or less.
Test the quality of your ground connection before applying power to the device.
Excess noise on the ground line can disrupt PS-B unit's operations.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Other
Device
Other
Device
PS-B unit
Summary of Contents for PS-4000B Series
Page 1: ...36 6HULHV 8VHU 0DQXDO...
Page 12: ...PS 4000B Series User Manual 12...
Page 14: ...PS 4000B Series User Manual 14...
Page 60: ...PS 4000B Series User Manual 60...
Page 74: ...PS 4000B Series User Manual 74...
Page 95: ...Hardware Modifications 95 The following figure shows the dimensions of the UPS battery unit...
Page 110: ...PS 4000B Series User Manual 110...
Page 112: ...PS 4000B Series User Manual 112...
Page 132: ...PS 4000B Series User Manual 132...
Page 134: ...PS 4000B Series User Manual 134...
Page 138: ...PS 4000B Series User Manual 138...