8
UL/c-UL/CSA Approval
The AGP3300-L1-D24/AGP3300-S1-D24/AGP3300-T1-D24/AGP3301-L1-D24/AGP3301-S1-D24/AGP3302-B1-D24
are UL/c-UL/CSA listed products.
UL File No.E182139
UL File No.E220851
AGP3300-L1-D24 (UL/CSA Registration Model:3280007-03)
AGP3300-S1-D24 (UL/CSA Registration Model:3280007-02)
AGP3300-T1-D24 (UL/CSA Registration Model:3280007-01)
AGP3301-L1-D24 (UL/CSA Registration Model:3280007-13)
AGP3301-S1-D24 (UL/CSA Registration Model:3280007-12)
AGP3302-B1-D24 (UL/CSA Registration Model:3280007-24)
These products conform to the following standards:
UL508
Industrial Control Equipment
UL1604
Electrical Equipment for use in Class I and II, Division 2, and Class III Hazardous (classified) locations.
CAN/CSA-C22.2 No.213-M1987
Safety Standard for Information Technology and Electrical Business Equipment
CAN/CSA-C22.2 No.14-95
Industrial Control Equipment
<Cautions>
Be aware of the following items when building the AGP into an end-use product:
•
The AGP unit's rear face is not approved as an enclosure. When building the AGP unit into an end-use product, be sure
to use an enclosure that satisfies standards as the end-use product's overall enclosure.
•
The AGP unit must be used indoors only.
•
Install and operate the AGP with its front panel facing outwards.
•
If the AGP is mounted so as to cool itself naturally, be sure to install it in a vertical panel. Also, insure that the AGP is
mounted at least 100 mm away from any other adjacent structures or machine parts. If these conditions are not met, the
heat generated by the AGP unit's internal components may cause it to fail to meet UL standards.
UL1604/CSA-C22.2, No.213 - Compliance and Handling Cautions
1. Power and input/output wiring must be in accordance with Class I, Division 2 wiring methods - Article 501-4(b) of
the National Electrical Code, NFPA 70 within the United States, and in accordance with Section 18-152 of the
Canadian Electrical Code for units installed within Canada.
2. Suitable for use in Class I, Division 2, Groups A, B, C, or D Hazardous Locations.
3. WARNING: Explosion hazard -substitution of components may impair compliance to Class I, Division 2.
4. WARNING: Explosion hazard -when in hazardous locations, turn the power OFF before replacing or wiring modules.
5. WARNING: Explosion hazard -confirm that the power supply has been turned OFF before disconnecting equip-
ment, or confirm that the location is not subject to the risk of explosion.
6. WARNING: Explosion hazard -do not connect/disconnect equipment unless area is known to be nonhazardous.
Port is for system setup and diagnostics.