background image

7

CLEANING AND MAINTENANCE

• 

Clean the product with a soft, dry cloth only. Do not use any solvents or abrasive 

chemical cleaners.

• 

The LED lamps in this product are non replaceable.

OPERATIONAL CHECKS

Fixing Hole

Wiring Entry

Legend diffuser

Test button

Fixing Hole

Battery Connector

LED Connector

Mains Connector

Note:

 This equipment must be checked regularly in compliance with local regulation and 

codes of practice. 

• 

The LED’s can be tested by pressing the TEST button on the bottom of the case. 

This simulates a power failure and the switches the lamp on to battery power.

• 

After installation, you should allow 24 hours for the battery pack to charge fully 

before testing. 

• 

Isolate the power supply and check that the lamp remains illuminated for at least 

three hours. Restore the power supply.

• 

Each day: Check that the green charging LED is lit.

• 

Each month (short test): Isolate the power supply and check that the lamp remains 

illuminated. Record the results on the test record sheet included with these 

instructions.

• 

Every six months: Isolate the power supply and check that the lamp remains 

illuminated after 1 hour. Record the results on the included test record. 

• 

Once each year: Isolate the power supply and check that the lamp is still illuminated 

after 3 hours. Record the results on the included test record. 

Please keep these test records in a safe place. A fire officer or other authorised 

person may want to see your record of inspection and testing.

LED status indicators

GREEN - Charging

YELLOW - Fault

RED - Power

Reviews: