7
CLEANING AND MAINTENANCE
•
Clean the product with a soft, dry cloth only. Do not use any solvents or abrasive
chemical cleaners.
•
The LED lamps in this product are non replaceable.
OPERATIONAL CHECKS
Fixing Hole
Wiring Entry
Legend diffuser
Test button
Fixing Hole
Battery Connector
LED Connector
Mains Connector
Note:
This equipment must be checked regularly in compliance with local regulation and
codes of practice.
•
The LED’s can be tested by pressing the TEST button on the bottom of the case.
This simulates a power failure and the switches the lamp on to battery power.
•
After installation, you should allow 24 hours for the battery pack to charge fully
before testing.
•
Isolate the power supply and check that the lamp remains illuminated for at least
three hours. Restore the power supply.
•
Each day: Check that the green charging LED is lit.
•
Each month (short test): Isolate the power supply and check that the lamp remains
illuminated. Record the results on the test record sheet included with these
instructions.
•
Every six months: Isolate the power supply and check that the lamp remains
illuminated after 1 hour. Record the results on the included test record.
•
Once each year: Isolate the power supply and check that the lamp is still illuminated
after 3 hours. Record the results on the included test record.
Please keep these test records in a safe place. A fire officer or other authorised
person may want to see your record of inspection and testing.
LED status indicators
GREEN - Charging
YELLOW - Fault
RED - Power