VVR - MANUAL
26 | VVR– Manual | AntecControls.com
Configuring a POT Curve for FHC
STEP 1
Ensure the unit has power.
NOTE:
Please see the FHC Manual for power requirements
STEP 2
Using the Ethernet cable described in the
Required Tools
, connect the RJ45 end to the
NET OUT port on the FHC and wire the 3-wire connection to the BCT using the
following wiring:
BCT Terminal
Wire Colour (PIN)
MS/TP COM
Brown (PIN 8)
MS/TP A+
Orange/White (PIN 1)
MS/TP B-
Orange (PIN 2)
STEP 3
Connect the BCT to the laptop using the USB-A to USB-B cable.
STEP 4
Open the Field Flash program.
CAUTION
If experiencing connection issue to the
FHC, unplug any unneeded USB devices
and disconnect any Bluetooth devices
from the computer before starting the
program.