20 | VVR– Manual | AntecControls.com
STEP 12B
Wire the:
1.
Actuator signal wire to AO1 on the FHC.
2.
POT cable to the Venturi POT terminal on the FHC.
3.
Power into the power terminal block on the FHC.
STEP 12C
Wire the:
1.
Actuator signal wire to AO1 on the LMX.
2.
POT cable to the Venturi POT terminal on the LMX.
3.
Flow and pressure signal into the FLO SIG and PRESSURE SIG terminal blocks,
respectively.
4.
Power into the power terminal block on the LMX.
STEP 13
Route the other end of the pressure tubing through the knockout holes to the Pace pressure
taps. Connect the red tubing to the high pressure side (H) and the green tubing to the low
pressure side (L).
NOTE:
For the LMX and FHC the tap marked with green is for low pressure and the tap
marked with red is for high pressure.
Pressure Signal
Venturi
Power
Flow Signal
Actuator
Power
Venturi POT