C
IMPORTANT Please read these instructions prior to installation. Refer to the Prima catalog for proper lamp type and maximum wattage for fixtures.
Prima is not responsible for any fixture or system failure caused by unsupported lamps. Contact Prima customer service for the latest updates on
which lamps we support and proper usage. Prima low voltage transformers must be used with all Prima Lighting product installations. All warranties
are void if Prima transformers are not used. Prima’s catalogs provide general information and suggestions for proper dimmer usage. Please consult
our customer service department with any questions regarding dimmer specifics. Prima is not responsible for any damage caused by improper
dimmer specification and usage. Use only qualified electrician for installation. Adhere to all local and national electrical codes prior to installation.
It is strongly recommended that gloves are used when handling the FIT I System track. Oils and dirt from fingers can sometimes permanently
mark the finish. Track should be cleaned with a damp cloth and thoroughly dried before fixture installation.
FIT I System adapter are installed in the track using a twist-and-lock method. The adapter is inserted at the desired location on the track
length. Pressure is applied on the adapter to compress the internal contact/pressure mechanism. While applying said pressure, the
adapter is rotated 90º clockwise until it stops. To secure the adapter, the knurled locking ring is rotated clockwise by hand until sufficient pressure
creates a solid and secure mounting. IMPORTANT: Do not attempt to slide the adapter to other locations on the track length after it is installed. The
adapter must be completely removed from the track slot and reinstalled at the new location.
Insert the adapter into the
track slot
Apply pressure and
rotate 90º clockwise
After rotation,
adapter rests
inside track slot.
Rotate knurled
locking ring
clockwise to
secure the adapter.
There should now
be a gap between
the two knobs.
C1
D1
D2
D3
D4
D5
C2
C3
C4
C5
Ensure that there is
no gap between
the knurled knobs
before installation.
Rotate knurled
locking ring
clockwise to
secure the adapter.
There should now
be a gap between
the two knobs.
Ensure that there is
no gap between
the knurled knobs
before installation.
FIT I SYSTEM TRACK REQUIRES SUPPORT POINTS BE INSTALLED EVERY 4’
FIT I SYSTEM TRACK REQUIRES SUPPORT POINTS BE INSTALLED EVERY 4’
D
l mounted
support. The following steps cover the general task of inserting the support adapter into the track slot. See the individual steps for various
support method installation instructions. It is strongly recommended that gloves are used when handling the FIT I System track. Oils and dirt
from fingers can sometimes permanently mark the finish. Track should be cleaned with a damp cloth and thoroughly dried before fixture
installation.
FIT I System support adapters are installed in the track using a twist-and-lock method. The support adapter is inserted at the desired
location on the track length. The adapter is rotated 90º clockwise until it stops. With a stem suspended support adapter, it will be
necessary to SLIGHTLY loosen the stem coupler to allow the adapter to rotate and lock into the track slot. To secure the adapter, the knurled
locking ring is rotated clockwise by hand until sufficient pressure creates a solid and secure mounting. IMPORTANT: Do not attempt to slide the
adapter to other locations on the track length after it is installed. The adapter must be completely removed from the track slot and reinstalled at the
new location.
Insert the support adapter
into the track slot
Loosen the set screw with
the supplied hex wrench.
(for stem only)
Rotate the adapter 90º
until the track rests on
the adapter.
Tighten the set screw
with the hex wrench.
(for stem only)
fit I system fixture adapter installation
Follow all local and national electrical codes.
For assistance please call Prima Customer Ser
vice at 562-407-3079
fit I system vertical support adapter installation
13615 Marquardt Ave. Santa Fe Springs, CA 90670
Ph. 562-407-3079 . Fx. 562-407-3069
www.primalighting.com
Black top knob is for
locking purposes.
Hold the bottom knob with
your fingers. Do not use a
plier or any other tools that
will hurt the adapter and finish.
REV
.033015
C
D
prima fit I system
general installation instructions part 2 of 12