Safety Shut-off Valve Leak Test
The safety shut-off valve leak test is only to be performed by a qualified technician. A leak (bubble) test should be performed on an
annual basis to ensure a proper seal. A very small amount of leakage is normal.
Inspect and Clean Gas Burner
Remove burner tray and inspect flame and spark rod for cracks or other damage. Check ceramic for cracks or chips. Replace if
damaged. Clean spark and flame rods with emery cloth. Inspect wires and replace if damaged.
Coil Winterization
NOTICE - IMPROPER FREEZE PROTECTION CAN LEAD TO UNIT AND BUILDING DAMAGE:
In climates where freezing conditions occur,
some form of freeze protection must be followed to avoid coil damage and subsequent leaks that can damage the unit and
the building. Damage from improper freeze protection will void the warranty.
In climates where freezing conditions may occur, some form of freeze protection for water coils is required. Coils can be drained
and blown out with compressed air to ensure no water remains. Alternatively, some form of antifreeze rated for the expected
ambient temperatures can be used. Antifreeze reduces the coil performance. If the coil was not designed for antifreeze, some
amount of coil performance loss can be expected.
Service and Warranty Procedure
Replacement Parts
Replacement parts can be obtained from Price Industries at [email protected] or 1-866-632-0066. When
contacting Price for replacement parts, refer to the model number and serial number on the name plate.
Warranty Parts
See limited warranty below for what is covered. Contact Price Industries at [email protected] or 1-866-632-0066
for warranty parts instructions. Have the unit model number and serial number available. The warranty part may need to be
returned to Price to obtain a new warranty part. Price Industries reserves the right to repair or replace a part under warranty.
25