5

 

Alarm and error handling 

 

5.1

 

Multi-F 

5.1.1

 

Alarm button 

There is a red alarm button on the right side of the switch panel. The red button will light up as soon as the Multi-F controller of the 
N-Gen nitrogen generator receives an alarm signal. The Multi-F controller has 1 digital input to which an alarm signal can be 
connected. These can be alarm signals of, for example, temperature protection or thermal protection of the compressor or a 
pressure switch that indicates the minimum compressed air pressure of the nitrogen generator. Which alarm it is depends on what 
is connected to the digital input. This will usually be the pre-pressure alarm for the N-Gen nitrogen generator, which indicates that 
there is too little compressed air pressure for the nitrogen generator. By pressing the button an attempt can be made to reset the 
alarm.   

Reset

 

Figure 8. Alarm button no alarm 

Reset

 

Figure 9. Alarm button active alarm 

 

5.1.2

 

Faults and alarms 

When an alarm occurs, this will be reported via the red button on the side of the switch panel. It lights up when one or more alarms 
have occurred. The N-Gen nitrogen generator therefore has two alarm levels.  
 
 

 

 
 
 
If one of the alarms occurs, the nitrogen generator is stopped and the main valve and the drain valve are closed. The nitrogen 
generator is still completing its cycle. In short, during an alarm, the nitrogen generator will:  

-

 

Stop generating nitrogen; 

-

 

Close the drain valve; 

-

 

Close the main valve; 

-

 

Light up the red alarm button.  

The N-Gen will respond the same to each of the alarms below. All alarms have the same urgency and the priority of 
which depends primarily on the nitrogen demand from other machines.  

 
 
 

5.1.3

 

Alarm messages 

EEPROM errors 

F01 

Eeprom adres 

An address fault has occurred. 

F02 

Eeprom adr0 

,, 

F03 

Eepromcomm 

There is no communication with the Eeprom. 

Can errors 

F04 

Canbus halt 

The Canbus could not send or receive. 

F05 

CanrxFifo 

The receive buffer of the Canbus is full. 

F06 

CanrxMBox 

The receive messagebox of the Canbus is full. 

F07 

CantxFifo 

The send buffer of the Canbus is full. 

RTC errors 

F08 

RTC comm. 

There is no communication with the RTC. 

F09 

RTC new 

The RTC is not set. 

RS232 errors 

F10 

Uart1 rxFifo 

The receive buffer of the RS232 is full 

F11 

Uart1 txFifo 

The send buffer of the RS232 is full 

Alarm level: 0 

System free of faults. 
The red reset button is not lit. 

Alarm level: 1.

 

An alarm has occurred.  
The red reset button lights up. 

Summary of Contents for N-Gen

Page 1: ...N Gen nitrogen generator High Performance and Single tube User manual Type User manual Date March 2021 Version Revision Version 2 0 Revision 00 Status Approved Company PRESSCON Location Honselersdijk...

Page 2: ...Page 2 of 19...

Page 3: ...1 OPERATION OF THE N GEN NITROGEN GENERATOR 11 3 1 1 Compressed air supply 11 3 1 2 Nitrogen production 11 3 2 SCHEMATIC OVERVIEW OF THE N GEN NITROGEN GENERATOR 12 4 CONTROLLER 13 4 1 MULTI F CONTROL...

Page 4: ...rence is in the number of PSA tubes that are used to make nitrogen The High Performance version uses 2 PSA tubes and the Single tube version uses only 1 PSA tube The Single Tube generator is a simplif...

Page 5: ...tly from the output connection may cause intoxication The nitrogen quickly mixes with the ambient air so that at a distance of 0 5m from the nitrogen output connection it no longer poses a health risk...

Page 6: ...s with bare hands Use heat resistant clothing 3 DANGEROUS TO INHALE GAS Avoid the specified area or wear appropriate breathing equipment 9 MOVING PARTS Risk of getting stuck or injuries to limbs Turn...

Page 7: ...ents by providing an illustration and numbering the most important parts The compressor is not described because different brands can be used that come with their own manual 2 1 N Gen nitrogen generat...

Page 8: ...e 8 of 19 2 2 N Gen nitrogen generator High Performance H P N gen controller 2 2 14 7 FX Pre ve nt 12 1 3 3 5 13 6 11 8 4 Figure 2 Schematic illustration of the N Gen High Performance nitrogen generat...

Page 9: ...Page 9 of 19 2 2 14 7 FX Pre ve nt 12 1 3 3 5 13 11 8 4 8 8 6 15 8 16 Figure 3 Schematic illustration of the N Gen High Performance nitrogen generator...

Page 10: ...7 Compressed air inlet Push in connection that is used for connecting the compressor to the nitrogen generator This is commonly done with a 16mm nylon air hose 8 PSA control manifold A pneumatically c...

Page 11: ...mand will be generated directly or indirectly and the N Gen will start producing the nitrogen If there is no pressure vessel the system is controlled by an external or other contact Step 2 Nitrogen pr...

Page 12: ...mponents in the system communicate with each other N Gen Control Nitrogen generator Compressor Filter PSA valve 1 PSA valve 2 PSA valve 3 Nitrogenpressure OK NO Alarm Air pressure to low NO Drainvalve...

Page 13: ...board for measuring and controlling A N Gen nitrogen generator consists of one or more N Gen Controls For the N Gen Control two hardware versions can be used the JGA2000 and the JGA2024 These boards a...

Page 14: ...The N Gen nitrogen generator therefore has two alarm levels If one of the alarms occurs the nitrogen generator is stopped and the main valve and the drain valve are closed The nitrogen generator is s...

Page 15: ...d out the controller Please contact PRESSCON Also in case of technical failure questions or other issues you can contact PRESSCON at any time 5 2 N Gen control 5 2 1 Faults and alarms The error levels...

Page 16: ...Check compressed air filters Service engineer X Check output flow and purity Service engineer X Clean dirt catcher of compressor Service engineer X Replace the compressed air filters Service engineer...

Page 17: ...negligence accident or whatsoever The warranty includes checking repair or replacement if defective from proven equipment Faulty equipment which has been replaced shall become property of PRESSCON Reg...

Page 18: ...has been added to the document Revision _R01 to _R02 indicates Correction an image language error or text error has been corrected Version Date Modification 1 1_R00 20 04 2020 Manual version 1 1_R00 t...

Page 19: ...rking with a product of PRESSCON Its aim is to maintain and possibly improve the quality of its products If additional information or support is requested then PRESSCON can be consulted through the fo...

Reviews: