Helios PD2-6200 Analog Input Flow Rate/Totalizer
Instruction Manual
9
Specifications
Except where noted all specifications apply to
operation at +25°C.
General
Display
Dual-line: 1.8" (46 mm) high, red LEDs
6 digits per line (-99999 to 999999), with
lead zero blanking
Display
Intensity
Eight user selectable intensity levels.
Default value is six.
Display
Update Rate
5/second (200 ms)
LED Status
Indicators
See
on page
details.
Overrange
Display flashes
999999
Underrange
Display flashes
-99999
Display
Assignment
Display Line 1:
Rate, total, grand total, alternate (rate/total,
rate/grand total, rate/units, total/units, and
grand total/units), set points, max/min, and
Modbus input.
Display Line 2:
Same as Display Line 1; plus units, tag or
turned off.
Additional displays are available if
parameter total is off, and parameter
d-SCAL is on: gross weight, gross & net
weight, PV1, PV2, and PCT
(refer to
Programming
Methods
Four programming buttons, digital inputs,
PC and MeterView Pro software, or
Modbus registers.
Noise Filter
Programmable from 2 to 199
(0 will disable filter)
Filter Bypass
Programmable from 0.1 to 99.9% of
calibrated span
Recalibration
All ranges are calibrated at the factory.
Recalibration is recommended at least
every 12 months.
Max/Min
Display
Max/min readings reached by the process
are stored until reset by the user or until
power to the meter is turned off.
Rounding
Select 1, 2, 5, 10, 20, 50, or 100
(e.g. rounding = 10, value = 123.45,
display = 123.50).
Password
Three programmable passwords restrict
modification of programmed settings and
two prevent resetting the totals.
Pass 1: Allows use of function keys and
digital inputs
Pass 2: Allows use of function keys, digital
inputs and editing set/reset points
Pass 3: Restricts all programming, function
keys, and digital inputs.
Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total
manually
Non-Volatile
Memory
All programmed settings are stored in
non-volatile memory for a minimum of ten
years if power is lost.
Power
Options
85-265 VAC 50/60 Hz; 90-265 VDC, 20 W max;
12-24 VDC, 12-24 VAC, 15 W max.
Powered over USB for configuration only.
Fuse
Required external fuse: UL Recognized,
5 A max, slow blow; up to 6 meters may
share one 5 A fuse
Normal Mode
Rejection
Greater than 60 dB at 50/60 Hz
Isolation
4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
Overvoltage
Category
Installation Overvoltage Category II:
Local level with smaller transient
overvoltages than Installation Overvoltage
Category III.
Environmental
Operating temperature range:
-40 to 65°C (-40 to 149°F)
Storage temperature range:
-40 to 85°C (-40 to 185°F)
Relative humidity:
0 to 90% non-condensing
Note: Printed circuit boards are conformally
coated.
Connections
Power, signal, relays, mA out: Removable
screw terminal blocks accept 12 to 22
AWG wire.
RS-485: Removable screw terminal block
accepts 16 to 30 AWG wire.
Digital I/O: Non-removable screw terminal
blocks accept 16 to 30 AWG wire.
Enclosure
UL Type 4X, IP65 rated. Polycarbonate &
glass blended plastic case, color: gray.
Includes four PG11 through-hole conduit
openings, with two factory installed PG11,
IP68, black nylon threaded hole plugs with
backing nuts.
Mounting
Wall Mounting:
Four (4) mounting holes provided for
mounting meter to wall. See
on page
for
additional details.
Pipe Mounting:
Optional pipe mounting kit (PDA6260)
allows for pipe mounting. Sold separately.
See
on page
for additional details.
Tightening
Torque
Power, signal, relays, mA out terminals:
5 lb-in (0.56 Nm)
Digital I/O and RS-485:
2.2 lb-in (0.25 Nm)
Overall
Dimensions
10.63" x 12.59" x 4.77"
(270 mm x 319.7 mm x 121.2 mm)
(W x H x D)
Weight
6.10 lbs (2.76 kg)
Warranty
3 years parts & labor. See Warranty
Information and Terms & Conditions on