Helios PD2-6200 Analog Input Flow Rate/Totalizer 

Instruction Manual 

 

40 

Scaling the 4-20 mA Analog 
Output (

Aout

The 4-20 mA analog output can be scaled to provide 
a 4-20 mA signal for any display range selected. 
No equipment is needed to scale the analog output; 
simply program the display values to the 
corresponding mA output signal. 
The 

Analog Output

 menu is used to program the  

4-20 mA output based on display values. 

For further details, see 

Setting Numeric Values

 

on page 

27, Analog Output Value for Loss of  

4-20 mA Input (Loop Break) 

on page

 46

. 

 

 

 

Reset Menu (

reset

The 

Reset

 menu is used to reset the totals and maximum 

or minimum reading (peak or valley) reached by the 
process; both may be reset at the same time by selecting 
“reset high & low” (

rst HL

). If 

total

 is set to 

no

, the tare 

value used to zero the display may be reset by selecting 
“reset tare” (

rst tr

). 

Manual Control Menu (

Contrl

The 

Manual Control

 menu is used to control the  

4-20 mA analog output and the relays manually, 
ignoring the input. Each relay and analog output can 
be programmed independently for manual control. 
Selecting automatic control sets all relays and analog 
output for automatic operation. 
 

 

 

Summary of Contents for Helios PD2-6200

Page 1: ...per Second Minute Hour or Day Total Grand Total or Non Resettable Grand Total Front Panel or Remote Total Reset Password Protection for Total Reset Total Stored in Non Volatile Memory Assign Any Relay...

Page 2: ...ete details Registered Trademarks All trademarks mentioned in this document are the property of their respective owners 2021 Precision Digital Corporation All rights reserved FREE MeterView Pro Progra...

Page 3: ...tion 16 Transmitter Supply Voltage Selection P P 17 Connections 18 Connectors Labeling 18 Power Connections 19 Signal Connections 19 Relay Connections 19 Switching Inductive Loads 20 RS 485 Connection...

Page 4: ...k Relay Force On Feature 39 Scaling the 4 20 mA Analog Output Aout 40 Reset Menu reset 40 Manual Control Menu Contrl 40 Setting Up the Password pass 41 Protecting or Locking the Meter 41 Total Reset P...

Page 5: ...r Powered by Internal Supply 19 Figure 12 Transmitter Powered by External Supply or Self Powered 19 Figure 13 Voltage Input Connections 19 Figure 14 Relay Connections 19 Figure 15 AC and DC Loads Prot...

Page 6: ...ial communications and digital I O features make the PD2 6200 an excellent addition to any system Using the PD2 6200 Like a PD2 6000 Process Meter The PD2 6200 is essentially a PD2 6000 process meter...

Page 7: ...1 MOD PD2LH3CB1 RYG Light Horn with Red Yellow Green Light Layers Button Mounted and Wired to Helios 1 Note 1 Specify MOD PD2LH model as a separate item on the order for the Helios to order the Light...

Page 8: ...and output functions including voltage current thermocouple and RTD PD9502 Low Cost Signal Generator The PD9502 is a low cost compact simple to use 4 20 mA or 0 10 VDC signal generator It can easily...

Page 9: ...Prevents resetting the total manually Gtotal Prevents resetting the grand total manually Non Volatile Memory All programmed settings are stored in non volatile memory for a minimum of ten years if pow...

Page 10: ...e with existing HART communications it displays the 4 20 mA primary variable and it allows the HART communications to pass through without interruption The meter is not affected if a HART communicator...

Page 11: ...gized in non alarm condition In case of power failure relay will go to alarm state Auto Initialization When power is applied to the meter relays will reflect the state of the input to the meter USB Co...

Page 12: ...C Digital Inputs Outputs Function Terminals provided for remote operation of all four programming operation buttons use PDA2364 MRUE control station Other uses include acknowledge reset relays and res...

Page 13: ...ocated under the lower door panel and are accessible by removing the single securing screw Wires should be run through the knockout holes located on the bottom of the meter see Figure 5 Conduit Holes...

Page 14: ...girth of the mounting screws pre drill holes at the mounting locations previously marked Insert mounting screws into the four mounting holes and screw them into the pre drilled holes DO NOT overtight...

Page 15: ...the top and bottom for vertical pipes or left and right for horizontal pipes of the reverse side of the meter enclosure using the provided fasteners DO NOT overtighten the fasteners as it could cause...

Page 16: ...ftware Video at www predig com meterviewpro MeterView Pro Installation 1 Connect one end of the provided USB cable to the meter and the other end to the computer The computer will automatically instal...

Page 17: ...ter requires 5 or 10 VDC excitation the switch labeled P P must be configured accordingly To access the voltage selection switch 1 Turn off the power to the meter 2 Unscrew and open the lower door pan...

Page 18: ...the lower door panel shows the location of all connectors available with the ordered configuration DO NOT connect any equipment to the RJ45 M LINK connector Otherwise damage will occur to the equipmen...

Page 19: ...are Figure 12 Transmitter Powered by Internal Supply Figure 13 Transmitter Powered by External Supply or Self Powered The current input is protected against current overload by an internal resettable...

Page 20: ...e load Part number PDX6901 Note Relays are de rated to 1 14th HP 50 watts with an inductive load RS 485 Connections The RS 485 connections are made to a five terminal connector used for Modbus RTU ser...

Page 21: ...DO Figure 21 Connections for RS 485 Connector to Serial Converter Three Wire Connection In order to wire the five pins for use as a three wire half duplex RS 485 connection it is necessary to create a...

Page 22: ...ons as illustrated in Figure 27 Meter to PDA2364 MRUE Control Station Figure 27 Meter to PDA2364 MRUE Control Station Connection Interlock Relay Feature As the name implies the interlock relay feature...

Page 23: ...ing buttons After power and input signal connections have been completed and verified apply power to the meter LED Status Indicators LED State Indication 1 4 Steady Alarm condition based on set and re...

Page 24: ...nd hold the Menu button for three seconds to access the advanced features of the meter Remote Buttons The meter can be operated via a remote control station PDA2364 MRUE using the digital input connec...

Page 25: ...nversion factor Program total conversion factor T rst Total reset Program total rest mode auto or manual GT tb Grand total time base Program grand total time base Display Functions Messages Display Pa...

Page 26: ...000 mA Dis 2 Display 2 Program display 2 value Out 2 Output 2 Program output 2 value e g 20 000 mA reset Reset Press Enter to access the Reset menu Rst Gt Reset grand total Press Enter to reset grand...

Page 27: ...hanged is displayed brighter than the rest Press and hold Up to auto increment the display value If negative numbers are allowed the first digit position will include a negative symbol after the 9 Pre...

Page 28: ...s 1 The totalizer continues working in the background 2 When selecting no for Total the meter now functions as a PD2 6000 Process Meter We strongly suggest that you download and use the PD2 6000 instr...

Page 29: ...be employed at a time The Scale and Calibrate functions can use up to 32 points default is 2 The number of points should be set in the Advanced menu prior to scaling and calibration of the meter See...

Page 30: ...o calibrate input 2 Not relevant when scaling the meter For instructions on how to program numeric values see Setting Numeric Values on page 27 Minimum Input Span The minimum input span is the minimum...

Page 31: ...hich the rate is multiplied before it is added to the total or grand total For Example if the rate was ten per second and the total conversion factor was 100 the total would increase by 1000 every sec...

Page 32: ...selecting d unit to display on line 2 will have the total appear on line 1 and the total unit appear on line 2 After setting up the input and the display press the Menu button to exit programming and...

Page 33: ...peration a On enabled b Off disabled 5 Time delay a On delay 0 999 9 seconds b Off delay 0 999 9 seconds 6 Relay action for loss break of 4 20 mA input ignore on off Relay Assignment Assign The relays...

Page 34: ...ts The fail safe operation is set independently for each relay Select on to enable or select off to disable fail safe operation Programming Time Delay The On and Off time delays may be programmed for...

Page 35: ...t go below the set point and then go above it Low Alarm Operation Set Reset For Manual reset mode ACK can be pressed anytime to turn off relay To detect a new alarm condition the signal must go below...

Page 36: ...the On time delay timer resets and the relay does not change state The same principle applies to the Off time delay Note If Automatic or Manual A nmAn reset mode is selected the LED follows the reset...

Page 37: ...lled and provide status indication for the following LED Status 1 Alarm 1 2 Alarm 2 3 Alarm 3 4 Alarm 4 The meter is supplied with four alarm points that include front panel LEDs to indicate alarm con...

Page 38: ...the signal passes the reset point alarm condition has cleared Acknowledging the alarm while it is still present has no effect on either the LED or the relay When the alarm is acknowledged after it ret...

Page 39: ...set the action to off 2 In the Advanced features User menu program any of the digital inputs to Force On any of the internal relays 1 4 3 Connect a switch or dry contact between the 5V terminal and t...

Page 40: ...alog Output Value for Loss of 4 20 mA Input Loop Break on page 46 Reset Menu reset The Reset menu is used to reset the totals and maximum or minimum reading peak or valley reached by the process both...

Page 41: ...e Grand Total has been programmed as non resettable the feature CANNOT be disabled Making Changes to a Password Protected Meter If the meter is password protected the meter will display the message Lo...

Page 42: ...ng rht Round horizontal tank Set meter for round horizontal tank volume calculation Inch Dimension cm Calculate volume in gallons or meters dianmr Diameter Enter the tank s diameter in inches Length L...

Page 43: ...than the bypass value are filtered or averaged by the meter The noise filter bypass may be set between 0 1 and 99 9 of full scale Rounding Feature round The rounding feature is used to give the user...

Page 44: ...mitters in open channel flow applications using weirs and flumes Application Open Channel Flow The PD2 6200 in combination with an ultrasonic level transmitter makes for an economical way to measure a...

Page 45: ...n be scaled to display the volume in any engineering units Another way to display the volume in liters is to enter the dimensions in cm The meter automatically calculates the volume in liters Low Flow...

Page 46: ...re used for scaling the 4 20 mA output in the Setup menu Analog Output Calibration Procedure 1 Wire the PD2 6200 4 20 mA output to a current loop that includes a power supply internal or external 12 t...

Page 47: ...the current display value relay states and analog output momentarily while the function key or digital input is active The process value will continue to be calculated in the background Ln1 Hi Displa...

Page 48: ...it is the active digit that can be changed by pressing the Up arrow button Press the Right arrow button to move to the next digit 6 Set the display value to correspond to the input signal being calibr...

Page 49: ...he inputs are triggered with a contact closure to 5 in the case of digital inputs 1 4 or with an active high signal see Digital I O Connections on page 21 for details The F4 is triggered with a contac...

Page 50: ...ts decimal points and relay indicators to enable the operator to check that all LEDs are functioning properly 4 Press the Enter button again to access the Information menu info or press the Menu butto...

Page 51: ...ent Asign2 Total Relay 3 assignment Asign3 Rate Relay 4 assignment Asign4 Rate Parameter Display Default Setting Relay 1 action Act 1 Automatic Relay 1 set point Set 1 1 000 Relay 1 reset point RSt 1...

Page 52: ...999 2 99999 Check 1 Input selected in Setup menu 2 Corresponding signal at Signal connector Display is unstable Check 1 Input signal stability and value 2 Display scaling vs input signal 3 Filter and...

Page 53: ...990 www predig com LIM2 6200_D SFT039 Ver 4 010 up 08 21 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800...