SuperNova PD500 PID Process & Temperature Controllers
Instruction Manual
58
Output Group (G.OUT), Address 800 - 899)
Address
D-register
Parameter
R/W
RAM
(Only)
DEC
HEX
DEC
HEX
40801
9F61
800
0320
CNT1
OUT1 output control selection
R/W
40802
9F62
801
0321
CNT2
OUT2 output control selection
R/W
40803
9F63
802
0322
O.ACT
Direct/reverse output action
R/W
40804
9F64
803
0323
CP
Heating control period
R/W
40805
9F65
804
0324
CPC
Cooling control period
R/W
40806
9F66
805
0325
HYS
Hysteresis
R/W
40807
9F67
806
0326
HYSC
Hysteresis (cooling)
R/W
40808
9F68
807
0327
EO
Heating emergency output
R/W
40809
9F69
808
0328
EOC
Cooling emergency output
R/W
40810
9F6A
809
0329
OL-H
Output high limit
R/W
40811
9F6B
810
0330
OL-L
Output low limit
R/W
Input Group (G.IN), Address 900 - 999
Address
D-register
Parameter
R/W
RAM
(Only)
DEC
HEX
DEC
HEX
40901
9FC5
900
0384
INP
Input Type selection
R/W
40902
9FC6
901
0385
UNIT
Unit selection
R/W
40905
9FC9
904
0388
DP-P
Dot point position selection
R/W
40906
9FCA
905
0389
SL-H
Scale high limit
R/W
40907
9FCB
906
038A
SL-L
Scale low limit
R/W
40908
9FCC
907
038B
RJC
Reference junction
compensation
R/W
40909
9FCD
908
038C
FILT
Input display value filter
R/W
40910
9FCE
909
038D
BIAS
PV bias
R/W
User Defined Modbus Map
It is possible to map the controller’s fixed Modbus registers to a set of Modbus D-registers from 1200 – 1219. These
user defined registers can be any Modbus registers from the set of tables above.
The user defined Modbus map is assigned using D-registers 721 – 740 (addresses 40722 – 40741). To create the
user defined Modbus map, write the D-register number of the desired parameters to D-register 721 (address 40722).
That parameter’s value will be available in Modbus D-register 1200 (address 41201).
For example, to configure a custom Modbus map of D-register 1200 to D-register 0 for NPV, D-register 1201 to
D-register 1 for NSV,
D-register 1202 to D-register 5 for MVOUT, D-register 1203 to D-register 207 for AT, D-register
1204 to D-register 210 for 1.P, D-register 1205 to D-register 211 for
1.C,
and D-register 1206 to D-register 212 for
1.D, set the user defined Modbus map as shown below.
Desired Parameter
Assignment
Address
Assignment
D-register
User Map
Address
User Map
D-Register
D-Register #
Parameter
Name
DEC
HEX
DEC
HEX
DEC
HEX
DEC
HEX
0
NPV
40722
9F12
721
02D1 41201
A0F1
1200
04B0
1
NSV
40723
9F13
722
02D2 41202
A0F2
1201
04B1
5
MVOUT
40724
9F14
723
02D3 41203
A0F3
1202
04B2
207
AT
40725
9F15
724
02D4 41204
A0F4
1203
04B3
210
1.P
40726
9F16
725
02D5 41205
A0F5
1204
04B4
211
1.I
40727
9F17
726
02D6 41206
A0F6
1205
04B5
212
1.D
40728
9F18
727
02D7 41207
A0F7
1206
04B6