SuperNova PD500 PID Process & Temperature Controllers
Instruction Manual
43
G.ALM Parameter Details
Parameter
Setting range
Unit
Default
Value
Parameter Display Condition
RET.T
PV, SV, MV
PV
Models with RET option only.
A1.TY
0 - 13
3
G.SUB parameter SUBx is ALM1
AL-1
Absolute: EU (0.0 - 100.0) %
Deviation: EUS (0.0 - 100.0) % Note 1
EUS 100.0% G.SUB parameter SUBx is ALM1
G.ALM parameter
A1.TY ≠ OFF (0)
A1.DB
EUS (0.0 - 100.0) %
Note 1
1.0
℃
A1.LS
RST, SET
RST
G.SUB parameter SUBx is ALM1
G.SUB parameter A1.LT is ON
G.ALM parameter
A1.TY ≠ OFF (0)
A2.TY
0 – 13
10
G.SUB parameter SUBx is ALM2
AL-2
Absolute: EU (0.0 - 100.0) %
Deviation: EUS (0.0 - 100.0) % Note 1
EUS 100.0% G.SUB parameter SUBx is ALM2
G.ALM parameter A2
.TY ≠ OFF (0)
A2.DB
EUS (0.0 - 100.0) %
Note 1
1.0
℃
A2.LS
RST, SET
RST
G.SUB parameter SUBx is ALM2
G.SUB parameter A2.LT is ON
G.ALM parameter A2
.TY ≠ OFF (0)
A3.TY
0 - 13
1
G.SUB parameter SUBx is ALM3
AL-3
Absolute: EU (0.0 - 100.0) %
Deviation: EUS (0.0 - 100.0) % Note 1
EU 100.0%
G.SUB parameter SUBx is ALM3
G.ALM parameter A3
.TY ≠ OFF (0)
A3.DB
EUS (0.0 - 100.0) %
Note 1
1.0 °C
A3.LS
RST, SET
RST
G.SUB parameter SUBx is ALM3
G.SUB parameter A3.LT is ON
G.ALM parameter A3
.TY ≠ OFF (0)
A4.TY
0 - 13
2
G.SUB parameter SUBx is ALM4
AL-4
Absolute: EU (0.0 - 100.0) %
Deviation: EUS (0.0 - 100.0) % Note 1
EU 0.0%
G.SUB parameter SUBx is ALM4
G.ALM parameter A4
.TY ≠
OFF (0)
A4.DB
EUS (0.0 - 100.0) %
Note 1
1.0
℃
A4.LS
RST, SET
RST
G.SUB parameter SUBx is ALM4
G.SUB parameter A4.LT is ON
G.ALM parameter A4
.TY ≠ OFF (0)
LB.TM
0 - 7200
Time
(sec)
480
G.SUB parameter SUBx is LBA
LB.SV
EUS (0.0 - 5.0)%
Note 1
EUS 0.15%
LB.DB
EUS (0.0 % + 1 digit) - 5.0 %
Note 1
EUS 0.15%
LB.LS
RST, SET
RST
G.SUB parameter SUBx is LBA
G.SUB parameter LB.LT is ON
1. Set by G.IN parameter UNIT.