SuperNova PD500 PID Process & Temperature Controllers
Instruction Manual
29
G.OUT Parameter Details
Parameter
Setting Range
Unit
Default
Value
Parameter Display Condition
CNT1
ONOF, PID
PID
CNT2
NONE, ONOF, PID
NONE
O.ACT
REV, DIR
REV
OUT2 control mode CNT2 is set
to NONE
CP
1 - 1000 s
Time
(seconds)
RLY : 20
SSR : 2
OUT1 option is RLY or SSR and
OUT1 control mode CNT1 is set
to PID.
CPC
1 - 1000 s
Time
(seconds)
20
OUT2 control mode CNT2 is set
to PID.
HYS
EUS (0.0 - 100.0) %
Note 1
1
OUT1 control mode CNT1 is set
to ONOF.
HYSC
EUS (0.0 - 100.0) %
Note 1
1
OUT2 control mode CNT2 is set
to ONOF.
EO
(-5.0 - 105.0) % (Note 2)
(0.0 - 105.0) % (Note 3)
%
0.0
EOC
(0.0~105.0) %
%
0.0
OUT2 control mode CNT2 is set
to ONOF or PID.
OL-H
(-5.0 - 105.0) % (Note 2)
(0.0 - 105.0) % (Note 3)
(However, OL-L < OL-H)
%
100.0
OUT1 control mode CNT1 is set
to PID.
OL-L
(-5.0~105.0) % (Note 2)
(0.0~105.0) % (Note 3)
(However, OL-L < OL-H)
%
0.0
OUT1 control mode CNT1 or
OUT2 control mode is set to PID.
1. Set by G.IN parameter UNIT.
2. Selections when thermocouple or RTD input type selected.
3. Selections when mA, VDC, or MVDC input type selected.