™ PD6363 Dual Analog Input Rate/Totalizer
Instruction Manual
9
Specifications
Except where noted all specifications apply to
operation at +25°C.
General
Display
Line 1: 0.60" (15 mm) high, red LEDs
Line 2: 0.46" (12 mm) high, red LEDs
6 digits each (-99999 to 999999), with lead
zero blanking
Display
Intensity
Eight user selectable intensity levels
Default value is six.
Display
Update Rate
Rate: 10 per second; up to 1 per 100
seconds (and is a function of Low Gate
setting); Total: 10 per second (fixed)
Overrange
Display flashes
999999
Display
Assignment
Display lines 1 & 2 may be assigned to
show:
•
One or more rate channels: Channel A
(Ch-A), B (Ch-B), or C (Ch-C)
•
Toggle between rate channels: Ch-A &
Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and
Ch-A, Ch-B, & Ch-C
•
Total or grand total: Ch-A or Ch-B
•
Rate and total or grand total:
Ch-A or Ch-B
•
Relay set points
•
Max and/or min values:
Ch-A, Ch-B, or Ch-C
•
Toggle between any rate channel &
units
•
Total and units: Ch-A or Ch-B
•
Toggle between totals:
Ch-A & Ch-B; Ch-A, Ch-B, and sum of
Ch-A and Ch-B
•
Modbus input
Line 2 may also be set to show engineering
units or be off, with no display.
Programming
Methods
Four front panel buttons, digital inputs, PC
and MeterView Pro software, or Modbus
registers.
Recalibration
All ranges are calibrated at the factory.
Recalibration is recommended at least every
12 months.
Max/Min
Display
Max/min readings reached by the process
are stored until reset by the user or until
power to the meter is turned off.
Rounding
Select 1, 2, 5, 10, 20, 50, or 100
(e.g. rounding = 10, value = 123.45,
display = 123.50).
Password
Three programmable passwords restrict
modification of programmed settings and
two prevent resetting the totals.
Pass 1: Allows use of function keys and
digital inputs
Pass 2: Allows use of function keys, digital
inputs and editing set/reset points
Pass 3: Restricts all programming, function
keys, and digital inputs.
Total: Prevents resetting the total manually
Gtotal: Prevents resetting the grand total
manually
Non-Volatile
Memory
All programmed settings are stored in non-
volatile memory for a minimum of ten years
if power is lost.
Power
Options
85-265 VAC 50/60 Hz; 90-265 VDC, 20 W max;
12-24 VDC, 12-24 VAC, 15 W max.
Powered over USB for configuration only.
Fuse
Required external fuse: UL Recognized, 5 A
max, slow blow; up to 6 meters may share
one 5 A fuse
Isolation
4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
Overvoltage
Category
Installation Overvoltage Category II:
Local level with smaller transient
overvoltages than Installation Overvoltage
Category III.
Environmental
Operating temperature range:
-40 to 65°C
Storage temperature range:
-40 to 85°C
Relative humidity:
0 to 90% non-condensing
Connections
Removable screw terminal blocks accept 12
to 22 AWG wire, RJ45 for external relays,
digital I/O, and serial communication
adapters.
Enclosure
1/8 DIN, high impact plastic, UL 94V-0,
color: black
Front Panel
NEMA 4X, IP65
Mounting
1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm)
Two panel mounting bracket assemblies are
provided.
Tightening
Torque
Screw terminal connectors: 5 lb-in (0.56 Nm)
Overall
Dimensions
4.68" x 2.45" x 5.64"
(119 mm x 62 mm x 143 mm)
(W x H x D)
Weight
9.5 oz (269 g)
Warranty
3 years parts & labor. See Warranty
Information and Terms & Conditions on
for complete details.