PD8-6300 Pulse Input Rate/Totalizer, Counter & Tachometer
Instruction Manual
54
Programmable Function Keys
User Menu (
user
)
The
User
menu allows the user to assign the front
programming buttons function keys F1, F2, and F3,
the digital input F4 (located on the input signal
connector), and four digital inputs (located on the
digital I/O connector to access most of the menus or
to activate certain functions immediately (e.g. reset
total, reset grand total, reset max & min, hold relay
states, etc.). This allows the meter to be greatly
customized for use in specialized applications.
The four digital outputs can be assigned to a number
of actions and functions executed by the meter (i.e.
reset total, reset grand total, alarms, relay
acknowledgement, reset or display max, min). The
digital outputs can be used to trigger external alarms
or lights to indicate these specific events.
Function Keys & Digital I/O
Available Settings
Refer to the following table for descriptions of each
available function key or digital I/O setting.
Function Keys & Digital I/O Available Settings
Display
Description
relay
Directly access the relay menu
Set 1*
Directly access the set point menu for
relay 1 (*through 4)
Rly d
Disable all relays until a button
assigned to
enable relays
(
Rly E
) is
pressed
Rly E
Enable all relays to function as they
have been programmed
O Hold
Hold current relay states and analog
output as they are until a button
assigned to
enable relays
(
Rly E
) is
pressed
d Hold
Hold the current display value, relay
states, and analog output momentarily
while the function key or digital input is
active. The process value will continue
to be calculated in the background.
Ln1 Hi
Display maximum display value on line 1
Ln1 Lo
Display minimum display value on line 1
Ln1 HL
Display maximum & minimum display
values on line 1
Ln2 Hi
Display maximum display value on line 2
Ln2 Lo
Display minimum display value on line 2
Ln2 HL
Display maximum & minimum display
values on line 2
Ln2 gt
Display the grand total on line 2
Function Keys & Digital I/O Available Settings
Display
Description
F On 1*
Force relay 1 (*through 4) into the on
state. This function is used in
conjunction with a digital input to
achieve interlock functionality.See
Setting Up the Interlock Relay (Force
On) Feature
on page
about interlock relays.
Contrl
Directly access the control menu
disabl
Disable the selected function key or
digital I/O
AcH
Acknowledge all active relays that are
in a manual operation mode such as
auto-manual or latching
Reset
Directly access the reset menu
Rst t
Reset the total
Rst gt
Reset the grand total
Rst Hi
Reset the stored maximum display
value
Rst Lo
Reset the stored minimum display
value
Rst HL
Reset the stored maximum &
minimum display values
Dsplay
Directly access the display menu
Line 1
Directly access the display line 1
menu
Line 2
Directly access the display line 2
menu
nmenu
Mimic the menu button functionality
(digital inputs only)
rigHt
Mimic the right arrow/F1 button
functionality (digital inputs only)
up
Mimic the up arrow/F2 button
functionality (digital inputs only)
Enter
Mimic the enter/F3 button functionality
(digital inputs only)
Alnm 1*
Provide indication when alarm 1
(*through 4) has been triggered (digital
outputs only)
Summary of Contents for ProtEX-MAX PD8-6300
Page 2: ...2 ...
Page 62: ...PD8 6300 Pulse Input Rate Totalizer Counter Tachometer Instruction Manual 62 NOTES ...
Page 63: ......