4222MCM101 3
OUTPUT
FREQUENCY LOW
/ PULSE LOW
20
20
2
R/W
UNSIGNED
INTEGER
Frequency output
low value in mHz or
1/1000nds of pulses
per min./hour/day
Range with frequency selected: 0...25000000
Range with p/min. selected:
60...30000000
Range with p/hour selected:
3600...30000000
Range with p/day selected: 86400...30000000
OUTPUT
FREQUENCY HIGH
/ PULSE HIGH
21
22
2
R/W
UNSIGNED
INTEGER
Frequency output
high value in mHz or
1/1000nds of pulses
per min./hour/day
Range with frequency selected: 0...25000000
Range with p/min. selected:
60...30000000
Range with p/hour selected:
3600...30000000
Range with p/day selected: 86400...30000000
OUTPUT
CUTOFF
FREQUENCY /
PULSE
22
24
2
R/W
UNSIGNED
INTEGER
Cutoff frequency in mHz
or 1/1000nds of pulses
per min./hour/day
Range with frequency selected: 0...25000000
Range with p/min. selected:
60...30000000
Range with p/hour selected:
3600...30000000
Range with p/day selected: 86400...30000000
OUTPUT
PULSE TIME
23
26
1
R/W
UNSIGNED
INTEGER
Pulse length in ms,
must be set less than 0.9
x (1 / Fmax)
Range:
1...1000
OUTPUT
INDICATE ERROR
24
27
1
R/W
UNSIGNED
INTEGER
Use a specific
frequency to
indicate errors
NO
=
0
YES
=
1
OUTPUT
ERROR
FREQUENCY
25
28
2
R/W
UNSIGNED
INTEGER
Frequency to
indicate an error in mHz
or 1/1000nds of pulses
per min./hour/day
Range with frequency selected: 0...26250000
Range with pulse selected:
0...31500000
OUTPUT
RESPONE TIME
26
30
1
R/W
UNSIGNED
INTEGER
Response time in 1/10 s
Range for non-temperature inputs: 4...600 (0.4...60 s)
Range for temperature inputs:
10...600 (1...60 s)
OUTPUT
OUTPUT LOW
27
31
2
R/W
INTEGER
Specific output
value low. Dependant of
selected input.
For temperature types
value is 1/10°.
Range equals the measurement range for the selected
sensor type and must be lower than OUTPUT HIGH
OUTPUT
OUTPUT HIGH
28
33
2
R/W
INTEGER
Specific output
value high. Dependant
of selected input.
For temperature types
value is 1/10°.
Range equals the measurement range for the selected
sensor type and must be higher than OUTPUT LOW
DISPLAy
DISPLAY
CONTRAST
29
35
1
R/W
UNSIGNED
INTEGER
Contrast in the LCD
display
Range: 0...9
DISPLAy
DISPLAY
BACKLIGHT
30
36
1
R/W
UNSIGNED
INTEGER
Backlight intensity in
LCD
Range: 0...9
DISPLAy
TAG TEXT
31
37
3
R/W
ASCII CHAR
Tag of the device
(6 characters)
Range: ASCII values from 32 to 90 (‘ ‘ to ‘Z’).
DISPLAy
LINE 3 FUNCTION 32
40
1
R/W
UNSIGNED
INTEGER
Information shown
in line 3 of display in
monitor mode (normal
mode). Choose between
the output
frequency value or the
configured tag.
Output value
=
0
TAG
=
1
INPUT
USE CALIB
33
41
1
R/W
UNSIGNED
INTEGER
Use the applied calibra-
tion values
NO
=
0
YES
=
1
GENERAL
ENABLE
PASSWORD
34
42
1
R/W
UNSIGNED
INTEGER
Password
protect entry to
configuration menu
NO
=
0
YES
=
1
INPUT
CALIB RANGE
LOW
35
43
2
R/W
FLOAT
Actual process value for
low calibration point in
either display values or
1/10 °C
For non-temperature input types range is DISPLAY
LOW...DISPLAY HIGH
For temperature input types the range equals the
measurement range for the selected sensor type
INPUT
CALIB RANGE
HIGH
36
45
2
R/W
FLOAT
Actual process value for
high calibration point in
either display values or
1/10 °C
As CALIB RANGE LOW
INPUT
CALIB POINT LOW 37
47
2
R/W
FLOAT
Measured process value
for low calibration point
in either display values
or 1/10 °C. (Must be cop-
ied from PROCESS DATA)
As CALIB RANGE LOW
INPUT
CALIB POINT
HIGH
38
49
2
R/W
FLOAT
Measured process value
for high calibration point
in either display values
or 1/10 °C
(Must be copied from
PROCESS DATA)
As CALIB RANGE LOW
GENERAL
HELP TEXT
LANGUAGE
39
53
1
R/W
UNSIGNED
INTEGER
Language for the help
texts shown in display
UK
=
0
DK
=
1
DE
=
2
FR
=
3
SE
=
4
IT
=
5
ES
=
6
GENERAL
CHECKSUM
100
100
1
RO
UNSIGNED
INTEGER
CRC16 checksum of the
configuration
Range 0...65536
GENERAL
Configuration
counter
101
101
1
R0
UNSIGNED
INTEGER
This counter will count
the number of times the
configuration has been
changed. The counter is
reset on power-up
Range 0...65536