FM Installation drawing 6333QF01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Revision date:
2014-09-17
Version Revision
V1R0
Page:
2/2
Installation notes.
The Transmitter must be installed in a suitable enclosure to meet installation codes stipulated in The
National Electrical Code (ANSI-NFPA 70).
To assure a Non-Incendive system the transmitter and associated apparatus must be wired in
accordance with the associated apparatus manufacturers field wiring instructions and the circuit
diagram shown above.
.
Non Hazardous Location
Hazardous (Classified ) Location
Class I, Division 2, Group A,B,C,D T4..T6
Class I, Zone 2, IIC T4..T6
Terminal:
11,12,13 and
21,22,23
Vmax: 35 VDC
Li: 10μH
Ci: 6.2nF
T6: -40 ≤ Ta ≤ 60ºC
T4: -40 ≤ Ta ≤ 85ºC
13
12
43
42
41
+
-
23
22
53
52
51
+
-
Associated
apparatus
6333A1A: one channel
6333A1B: two channel
CH2
CH1
11
21
Associated
apparatus
20 6333V104-DE