10
User Manual
neuro 104
Parameter Description
Settings
(Default Value)
Setpoint Low to Setpoint High
(Default :
-200)
Setpoint Low to Setpoint High
(Default :
-200)
PROFILE ABORT COMMAND
This parameter is available and applicable only if its availability in
Operator Parameter list is enabled under supervisory level in
PAGE- 13 parameter list and Profile Cycle is already started. It has
two possible settings. It serves as a Command to abort (stop) the
running Profile Cycle and the Profile Cycle status indication.
The two possible settings are:
(a) No
As an annunciation, this indicates that the Profile Cycle has not
been aborted and is currently in running state.
If the Profile Cycle is not to aborted yet, issue this as a Command
to continue the running Profile Cycle.
(b) Yes
If for any reason, the running Profile Cycle is required to stop,
issue this Command. This Command aborts (stops) the running
Profile Cycle
CONTROL SETPOINT
This is the default active Setpoint that the controller respects for
the control purpose. The controller attempts to maintain (regulate)
the PV
at this Setpoint unless the Manual or Standby mode is
activated or a Profile Cycle is running.
The Control Setpoint (SP) is expressed in the same unit and
resolution as that for PV. If the parameter ‘Input Type’ is altered in
PAGE-12 parameter list, the Control Setpoint (SP) value
automatically set to Minimum Range specified for the altered
‘Input Type’. It is, therefore, imperative that this parameter value
be re-adjusted to the required value after configuring the controller
for a new ‘Input Type’. This parameter could also be adjusted on
Lower Readout in MAIN
display if Set-up Mode is enabled in
PAGE-13 parameter list.
AUXILIARY SETPOINT
This is an Auxiliary Setpoint, available and applicable only if
Auxiliary Setpoint mode is enabled (by selecting the option to
‘Auxiliary Setpoint’) in PAGE-13 parameter list and the respective
hardware module is fitted.
This Setpoint is activated only if the controller detects the potential
free contacts closure or Digital Pulse voltage less than 0.5 V via
the Auxiliary Setpoint selection hardware module. When
activated, the controller attempts to maintain (regulate) the PV
at
the Auxiliary Setpoint (ASP).The Auxiliary Setpoint is treated
same as Control (Main) Setpoint (described above) except for
No
Yes
(Default :
No)