30
第
十
章
Section IX
Soft-start model specifications and
options
9-1
PR5200(C) series soft starter (5.5KW-55KW) list of the external parts of the
specification reference
:
Soft starter model
Rated
Power
(KW)
Rated
current
(A)
Supporting
circuit breaker
model (QF)
Supporting the
bypass
contactor
model
pporting
the
bypass
contactor type
(KM)
A line size
Remarks
PR5200
5R5G3
5.5
11
16A
25A
2.5mm2 Cable
Rated power and
rated current is the
maximum rating of
the
soft
starter,
matching
circuit
breaker
and
the
bypass
contactor
should match the
size
of
motor
specification.
PR5200
7R5G3
7.5
15
20A
25A
4mm2 Cable
PR5200
011G3
11
22
32A
40A
6mm2 Cable
PR5200
015G3
15
30
40A
63A
10mm2 Cable
PR5200
018G3
18
37
50A
63A
10mm2 Cable
PR5200
022G3
22
44
63A
63A
16mm2 Cable
PR5200
030G3
30
60
80A
100A
25mm2 Cable
PR5200
037G3
37
74
100A
160A
35mm2 Cable
PR5200
045G3
45
90
125A
160A
35mm2 Cable
PR5200
055G3
55
110
160A
160A
35mm2 Cable
PR5200
075G3
75
150
180A
250A
30*3mm2 Cable
PR5200
090G3
90
180
225A
250A
30*3mm2 Cable
PR5200
115G3
115
230
315A
400A
30*3mm2 Cable
PR5200
132G3
132
260
315A
400A
30*4mm2 Cable
PR5200
160G3
160
320
350A
630A
30*4mm2 Cable
PR5200
185G3
185
370
400A
630A
40*4mm2 Cable
PR5200
200G3
200
400
500A
630A
40*4mm2 Cable
PR5200
250G3
250
500
630A
630A
40*4mm2 Cable
PR5200
280G3
280
560
630A
1000A
40*4mm2 Cable
PR5200
320G3
320
640
800A
1000A
40*4mm2 Cable
PR5200
400G3
400
800
1000A
1000A
40*4mm2 Cable