Chapter 2 Standard specifications
8
Ch
ap
ter
2
Remark:
(1) PI500 frequency inverter PI500 132G3 to PI500 400G3, with “R”means built-in DC
reactor, for example PI500 160G3R, PI500 160G4R .
(2) The correct option of frequency inverter is : Rated output current of frequency inverter
≧
rated current of motor, and the capacity of overload should be considered;
The power difference between rated power of frequency inverter and motor should be less
than two class;
While big frequency inverter loading smaller motor, the correct motor parameters should be
input in case the motor be damaged by overload.
2-2.Standard specifications
Items
Specifications
Power
input
Rated voltage
AC 1PH 220V(-15%) to 240V(+10%)
AC 3PH 220V(-15%) to 240V(+10%)
AC 3PH 380V(-15%) to 440V(+10%)
AC 3PH 480V(-10%) to 480V(+10%)
Input frequency
50Hz/60Hz
Allowable
fluctuation
Voltage:±10%
Voltage unbalance rate is less than 3%
Input frequency:±5%;
Aberration rate meet IEC61800-2
standard
Control
system
Control system
High performance vector control inverter based on DSP
Control method
V/F control, vector control W/O PG,
Automatic torque
boost function
Realize low frequency (1Hz) and large output torque control under
the V/F control mode.
Acceleration/dec
eleration control
Straight or S-curve mode. Four times available and time range is
0.0 to 6500.0s.
V/F curve mode
Linear, square root/m-th power, custom V/F curve
Over load
capability
G type:Rated current 150% -1 minute, rated current 180%-2seconds
F type:Rated current 120% -1 minute, rated current 150%-2seconds
Maximum frequency 1.Vector control:0 to 300Hz; 2.V/F control:0 to 3200Hz
Carrier
Frequency
0.5 to 16kHz; automatically adjust carrier frequency according to
the load characteristics.
Input frequency
resolution
Digital setting 0.01Hz Minimum analog:0.01Hz
Start torque
G type:0.5Hz/150% (Vector control W/O PG)
F type: 0.5Hz/100% (Vector control W/O PG)
Speed range
1:100(Vector control W/PG)
Steady-speed
precision
Vector control W/O PG: ≤±0.5%(Rated synchronous speed)
Torque response
≤ 40ms (Vector control W/O PG)
Torque boost
Automatic torque boost; manual torque boost(0.1% to 30%)
DC braking
DC braking frequency: 0.0Hz to max. frequency, braking time:
0.0 to 100.0 seconds, braking current value: 0.0% to 100.0%
Jogging control
Jog Frequency Range: 0.00Hz to max. frequency;
Jog Ac/deceleration time: 0.0s to 6500.0s
Multi-speed
operation
Achieve up to 16-speed operation through the control terminal
Built-in PID
Easy to realize closed-loop control system for the process control.
Automatic voltage
regulation(AVR)
Automatically maintain a constant output voltage when the
voltage of electricity grid changes
Constant pressure
water supply
special function
Automatic pump increase, automatic pump reduction, low
pressure and high pressure alarm, multi-stage pressure water
supply time period and pressure setting, motor power frequency