Chapter 5 Function parameter
37
Ch
ap
ter
5
187
F8.01
Overcurrent stall protection
current
100% to 200%
-
☆
188
F8.02
Overload protection
selectiondvd
0:Invalid;1:valid
1
☆
189
F8.03 Overload protection gain
0.20 to 10.00
1.00
☆
190
F8.04 Overload pre-alarm coefficient 50% to 100%
80%
☆
191
F8.05 Over-voltage stall gain
0 to 100
0
☆
192
F8.06
Over-voltage stall protection
voltage / energy consumption
brake voltage
120% to 150%
130%
☆
193
F8.07
Input phase loss protection
selection
Unitsdigit:Input phase loss
protectionselection
0:Invalid 1:Enable
Tens digit:Contactor actuation
protection
0:Invalid 1:Enable
11
☆
194
F8.08
Output phase loss protection
selection
0:Invalid; 1:Enable
1
☆
195
F8.09 Short to ground protection
0:Invalid; 1:Valid
1
☆
196
F8.10 Number of automatic fault reset 0 to 32767
0
☆
197
F8.11 Fault DO action
0:OFF; 1:ON
0
☆
198
F8.12 Fault reset interval
0.1s to 100.0s
1.0s
☆
5-1-11.F9 group - Communication parameter
No.
Code
Parameter name
Setting range
Factory
setting
Chan
ge
199 F9.00 Baud rate
Unit:Modbus
0: 300BPS;; 1:600BPS; 2:1200BPS;
3:2400BPS; 4:4800BPS; 5:9600BPS;
6:19200BPS; 7:38400BPS; 8:57600BPS;
9:115200BPS
6005
☆
200 F9.01 Data format
0:Noparity (8-N-2) 1:Oddparity (8-E-1)
2:Evenparity (8-O-1) 3:Noparity (8-N-1)
0
☆
201 F9.02 This unit address
1 to 250,0 for broadcastaddress
1
☆
202 F9.03 Response delay
0ms to 20ms
2ms
☆
203 F9.04
Communication
timeout time
0.0(Invalid));0.1 to 60.0s
0.0
☆
204 F9.05
Date Transmission
format
Unitsdigit:MODBUS
0:Non-standard MODBUS protocol
1:StandardMODBUSprotocol
31
☆
205 F9.06 Current resolution 0:0.01A ; 1:0.1A
0
☆
5-1-12. Fb group-Controloptimization parameters
No.
Code
Parameter name
Setting range
Factory
setting
Chan
ge
206
Fb.00 Fast current limiting manner 0:Invalid 1:Enable
1
☆
207
Fb.01 Under-voltage point setting
50.0%to 140.0%
100.0%
☆