Specifications
67
Powerware
®
Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA)
Uncontrolled Copy
PPDM Outlets and Input and Output Cords
PPDM Model
Outlets
Input Cords
Output Cords
L6-30R/IEC 320-C19 PPDM
L6-30R (1)
IEC 320-C19 (1)
6-15R (2)
5-15R (8)
Detachable 2-meter cord with
L6-30R and L6-30P
IEC 320-C13/5-15P (1)
IEC 320-C13/6-15P (2)
IEC 320-C19/C20 (1)
IEC 309 PPDM
IEC 309 (1)
IEC 320-C13 (6)
IEC 320-C19 (1)
Connected cord with IEC 309
(3-pin 32A)
IEC 320-C13/C14 (3)
IEC 320-C19/C20 (1)
L6-30R/5-15R PPDM
L6-30R (2)
5-15R (8)
Detachable 2-meter cord with
L6-30R and L6-30P
Electrical Specifications for the Prestige 6000 with PPDM
Use the following tables to determine load wiring requirements when
the PPDM is used with the UPS. The distribution of your load on the
available outputs of the PPDM may affect the maximum load obtainable.
Prestige 6000 PPDM Ratings with a Model 6000 UPS
PPDM Model
Input Utility Voltage
and Selected UPS
Output Voltage
Input
Current
Output Voltage and
Maximum Current
Maximum Output
Apparent Power**
208:120/208
L6-30R/IEC 320-C19 PPDM
208 Vac
24A
120/208 Vac,
15.0/25.0A
5200 VA
208:120/208
L6-30R/5-15R PPDM
208 Vac
24A
120/208 Vac,
15.0/25.0A
5200 VA
240:240
IEC 309 PPDM
220 - 240 Vac
24A
220 - 240 Vac,
15.0/24.7A
5800 VA
240:120/240
L6-30R/5-15R PPDM
200 - 240 Vac
24A
100 - 120/200 - 240 Vac,
15.0/24.7A
5800 VA
*
Ratings based on 4000W load on PPDM, plus sufficient linear inductive load to achieve the current rating of the input
plug, not to exceed VA rating of PPU.
NOTE
Input and output currents are approximately the same when load is powered through bypass.