Installation
32
Powerware
®
Prestige Series Installation and Operator’s Manual for IBM Applications (6000 VA)
Uncontrolled Copy
UPS with PowerPass Distribution Module Installation
The PPDM has a Maintenance Bypass feature that supplies power to
your equipment even when the PPU is removed for maintenance or
upgrades. There are three PPDM models: the L6-30R/IEC 320-C19
PPDM, the IEC 309 PPDM, and the L6-30R/5-15R PPDM. The rear
panels of these models are shown in Figure 5 on page 33, Figure 7 on
page 34, and Figure 8 on page 35, respectively.
Use the following procedure to install the PPU and battery cabinets with
the PPDM:
1.
Place the UPS near the equipment to be protected. The UPS
should be well ventilated and away from direct sunlight or
other heat source.
Stack the PPU, battery cabinets, and PPDM as shown in
Figure 4.
If more than two batteries are to be used, place the batteries
next to the other batteries. (See the FCC Statement in the front
of this manual for more information on radio-frequency
emissions.)
NOTE
Do not connect more than six standard battery cabinets to the PPU. For
extended battery run times, contact your local distributor for additional battery
cabinets. Do not place more than six cabinets in one stack (the PPU is equal to two
cabinets and the PPDM is equal to two cabinets).
PPDM
PPU
Battery Cabinets
Air
Vents
Figure 4. UPS with PPDM