Installation
4
Powerware
®
5125 Installation Guide for IBM Applications
:
164201356 B
Uncontrolled Copy
Rack-Mount Setup
The UPS can be installed in 19-inch racks and needs only 2U of valuable
rack space.
C A U T I O N
The UPS and Extended Battery Module are heavy. A minimum of two people are
required to lift the UPS into the rack.
NOTE
Fixed mounting rails are required for each cabinet. If fixed rails are not already
installed in your rack, contact your local IBM representative to order a rail kit. If you
are installing the UPS in a non-IBM rack, contact your Powerware representative.
Use the following procedure to install the UPS in a rack:
1.
Place the UPS on a flat, stable surface with the front of the UPS
facing toward you.
2.
Attach the supplied mounting handles to the mounting
brackets (see Figure 1).
3.
If installing optional Extended Battery Modules, repeat Steps 1
and 2 for each cabinet.
Mounting Handle
Mounting
Bracket
Figure 1. Installing the Mounting Brackets
NOTE
The UPS and EBMs MUST be installed at the bottom of the rack. If placed in a
rack with existing equipment, the rack must be reconfigured to allow the UPS
installation at the bottom of the rack.
NOTE
The EBMs must be installed below the UPS as shown in Figure 2.
4.
Slide the UPS and any optional EBMs into the rack.
5.
Secure the units to the rack according to the rail kit
instructions.