CAUTION - To reduce the risk of fire, the unit connects only to a circuit
provided with branch circuit overcurrent protection for :
63A rating, for 6kVA models,
100A rating, for 10kVA models
The upstream circuit breaker for Normal AC/Bypass AC must be easily
accessible. The unit can be disconnected from AC power source by opening this
circuit breaker.
An additional AC contactor is used for backfeed protection and must comply
with IEC/EN 62040-1 (the creep age and clearance distances shall meet the
basic insulation requirements for pollution degree 2).
Disconnection and overcurrent protection devices shall be provided by others
for permanently connected AC input (Normal AC/Bypass AC) and AC output
circuits.
Check that the indications on the rating plate correspond to your AC powered
system and to the actual electrical consumption of all the equipment to be
connected to the system.
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the
equipment and shall be easily accessible
Never install the system near liquids or in an excessively damp environment.
Never let a foreign body penetrate inside the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry
place.
The admissible storage temperature range is -25°C to +60°C with battery(-15°C
to +40°C without battery).
Special precautions
The unit is heavy: wear safety shoes and use vacuum lifter preferentially for
handling operations.
All handling operations will require at least two people (unpacking, lifting,
installation in rack system).
Straps are provided only for unpacking manually the unit from the carton;
don’t use the straps to carry the unit around. The unit can slip from the straps
during handling (risk of injury and product damage):
- keep 12in / 30cm minimum distance between the straps
- lift the unit carefully and keep it at low height