31
Battery
remaining time
[enabled] [disabled]
[enabled]
Charger current [0~4] 0~4A for standard model
[0~12] 0~12A for long backup model
[1.4A] for 6K
[2A] for 10K
[4A] for 6KS/10KS
Site wiring fault
[disabled] [enabled]
[disabled]
LCD contrast
[-5 ~ +5]
[+0]
5.5 UPS startup and shutdown
Please make sure there is no load connected to the ups before the ups is turned
on, and take on the load one by one after the UPS is turned on.
Take off all of the connected loads before turning off the UPS.
Starting the UPS with utility
Verify that the total equipment ratings do not exceed the UPS capacity to
prevent an overload alarm.
Start the UPS with utility:
Check all the connection is correct.
Power on the UPS, the fan begins to rotate. After that, the LCD will show the
default UPS status summary screen.
Pressing
button continuously for more than 1 second, the buzzer will beep
300ms, UPS starts to turn on.
A few seconds later, the UPS turns into Line mode. If the utility power is
abnormal, the UPS will transfer to Battery mode without output interruption of
the UPS.
Starting the UPS on Battery
Before using this feature, the UPS must have been powered by utility power
with output enabled at least once.
After connect the UPS with battery, should wait 10s before pressing the
button for pre-charging the auxiliary power supply.
Battery start can be disabled. See “Start on battery” setting in user settings
refer to chapter 5.4.
To start the UPS on battery:
Check all the connection is correct.