Document A55-00042 Rev. I POWERVAR Mobile Power Manager
P a g e
| 37
Code
As displayed in MPMView What it means
24-063
Service Check: Replace
Battery – Date Threshold
This alarm is raised when the comparison of MPMView system date to
Battery Replace Date indicates that the battery Age is older than the
Battery Age Threshold. Default is 18 Months, configure via MPMView.
24-064
Service Check: Smart
Batteries - Configuration
This alarm is raised when the number of Smart Batteries detected is
different than expected by MPM configuration.
24-066
Service Check: Smart
Batteries - Communication
This alarm is raised when MPM unit has lost communication with a
SmartBattery. Could indicate Smart Battery has entered a Safe/Protect
Mode from being left depleted and without charge for too long. The alarm
may clear if the MPM unit is able to recover the battery. If the alarm
persists, check SmartBattery cable connections.
20-134 Service
Check:
Temperature Warning
This is the 1
st
level warning that the MPM internal temperatures are nearing
a level where immediate thermal shutdown could occur if temperatures
continue to increase. Check that MPM ventilation is unobstructed. If no
visible obstruction, MPM unit may need cleaning or other Service.
24-032
Service Check: Battery
Connection
The MPM unit detects no voltage across the battery terminals. Battery may
be disconnected, or there may be a blown fuse. The MPM can still power up
when connected to AC input line
30-189
Input Frequency Out Of
Range
This alarm is raised if the frequency of the input AC power to the MPM unit
is out of range and the output can only be supplied from battery power.
34-053
Battery Charge Threshold:
Low-Critical
Final warning to recharge battery – shutdown imminent. Hard coded within
MPM to be raised when charge level is less than 5%.
36-080
Output Overload
This alarm is raised if MPM detects its VA output is over 110%.
36-081
Output Overload
This alarm is raised if MPM detects its Watt output is over 110%.
33-037
Service Required: Charger
This alarm is raised if MPM charger delivers more than 110% of max charge
current for more than 60 seconds.
33-038
Service Required: Charger
This alarm is raised when MPM is attached to a Smart battery and battery
indicates an “OverCharged” alarm.
34-055
Service Warning: Smart
Battery Over Temp
This alarm is raised when MPM is attached to a Smart battery and battery
indicates its internal temperature has exceeded internal threshold.
30-190
Service Required: Output
Bad
MPM detects a problem in inverter or output circuits; output relay is
shorted, inverter voltage too high or too low, inverter failure or output fuse
open.
30-192
Service Required: EEPROM
failure
MPM detects a serious internal error. Return for Service.
Summary of Contents for MPM
Page 6: ...Document A55 00042 Rev I POWERVAR Mobile Power Manager P a g e 6 ...
Page 13: ...Document A55 00042 Rev I POWERVAR Mobile Power Manager P a g e 13 ...
Page 30: ...Document A55 00042 Rev I POWERVAR Mobile Power Manager P a g e 30 Physical Dimension Drawings ...
Page 31: ...Document A55 00042 Rev I POWERVAR Mobile Power Manager P a g e 31 ...