Document A55-00042 Rev. I POWERVAR Mobile Power Manager
P a g e
| 23
Technical Specifications # 87023-06R (82023-07R)
Feature
Specification
Output Power
150 VA / 150 Watts (250 VA/250 watts)
Input Voltage Range
Operating Range
Domestic: 120VAC Nominal (100-137* VAC) 60 Hz
International: 230VAC Nominal (195-265* VAC) 50/60 Hz
* If input VAC is within the range unit will assume valid AC input Operating Range.
.
Output Voltage
SOURCE = Battery
Domestic: 120VAC/60Hz.
International: 230VAC/50/60Hz.
SOURCE = AC Input: Output voltage depends on Input VAC.
Output will track Input -5% to +6% depending on Load & Charger state:
•
No load, charger idle, VAC may be 6% higher than input.
•
Full load and charger at full power VAC may be 5% lower than input
100 105 110 120 132 137
195 200 215 230 255 265
International:
Domestic: