10
A01-00030 Rev D
• The AC power supply for the UPM should be conveniently near the
UPM and easily accessible – avoid extension cords or temporary
power strips to power the UPM.
• The total leakage current of the UPM and consumer connected
equipment should not exceed 3.5 mA.
• Not for use in a computer room as defined in the Standard for the
Protection of Electronic Computer/Data Processing Equipment,
ANSI/NFPA 75.
• The socket-outlet shall be installed near the equipment and shall
be easily accessible.
• The battery should be disconnected from the UPM by unplugging
at its quick connectors when maintenance or service work inside
the UPM is necessary.
• Do not dispose of batteries in a fire – batteries may explode.
• Do not open or mutilate batteries. Doing so may release electrolyte
or other toxic substances, which may be harmful to the skin, eyes,
or the environment. A battery can present a risk of electric shock
and high short circuit current. The following precautions should be
observed when working with batteries:
• Remove watches, rings, or any other metal jewelry or objects
which may make contact with the battery.
• Use tools with insulated handles.
CAUTION
Risk of Energy Hazard, 12 V, 8.5 Ampere-hour battery for ABCEG251
and ABCEG401. Before replacing batteries, remove conductive
jewelry such as chains, wrist watches, and rings. High energy through
conductive materials could cause severe burns.
CAUTION
Risk of Energy Hazard, 24 V, 8.5 Ampere-hour battery for
ABCEG601. Before replacing batteries, remove conductive
jewelry such as chains, wrist watches, and rings. High energy
through conductive materials could cause severe burns.
Summary of Contents for GTS Series
Page 1: ...GTS Series User Manual ...
Page 24: ...24 A01 00030 Rev D Figure 2 250 400VA Figure 3 600VA ...
Page 25: ...25 A01 00030 Rev D 6 0 Specifications REAR PANEL 250VA MODELS INTERNATIONAL NORTH AMERICAN ...
Page 26: ...26 A01 00030 Rev D REAR PANEL 400VA MODELS INTERNATIONAL NORTH AMERICAN ...
Page 27: ...27 A01 00030 Rev D REAR PANEL 600VA MODELS INTERNATIONAL NORTH AMERICAN ...
Page 33: ...33 A01 00030 Rev D ...
Page 56: ...56 A01 00030 Rev D Figure 2 250 400VA Figure 3 250 600VA ...
Page 58: ...58 A01 00030 Rev D PANNEAU ARRIÈRE MODÈLES 400VA INTERNATIONAL AMÉRIQUE DU NORD ...
Page 59: ...59 A01 00030 Rev D PANNEAU ARRIÈRE MODÈLES 600VA INTERNATIONAL AMÉRIQUE DU NORD ...
Page 65: ...65 A01 00030 Rev D ...