Service Manual
Chapter 5 - Functional description
Battery Charger CS0074
5 - 4
3x3 UPS Functional description
Issue 2 - November 2001
5.4 - Battery Charger CS0074
The battery charger used in the UPS is a PWM controlled `Buck/Boost' DCĆDC converter which
produces a battery recharge float voltage of 230 Vdc.
The principals circuit components are:
a)
Power section (PD1Ć2, LI, Q1, Dl, L2).
b)
Supply section (+l5Vdc, Ć 6.2 Vdc).
c)
PWM generation and feedback section (U10 Ć U3).
d)
The battery test section (U4).
The input mains voltage is rectified by the diode bridge PD1 and PD2, steppedĆdown by the main power
components L1, D1, L2 with the voltage stabilised by the switching of IGBT Q2 the PWM gate drive signal
generated by U10. This configuration produces a stable battery recharging float voltage of 432 Vdc.
5.4.1 - Battery Charger Voltage Adjustment
a)
P1 = adjusts the float voltage level to 432 Vdc
b)
P2 = adjusts the boost voltage level. This setting is dependant on the type of battery
fitted.
c)
P3 = adjusts the float voltage when the temperature compensation option is enabled.
5.4.2 - Link and Jumper Functions
a)
JPI ĆJP2 sets the recharging current.
Link/Amper
e
IA
3A
5A
JPI
open
open
close
JP2
open
close
open
b)
JP3 enable/disables the boost charge.
Link
Boost Disable
Boost Enable
JP3
open
close
c)
JP4 enable/disables the temperature compensation circuit.
Link
Th Comp.
Disable
Th. Comp.
Enable
JP4
open
close
d)
Jumpers JP5 to JPI0 set the capacity for the installed battery, this is used for the battery
test function.
Link
JP10
JP9
JP8
JP7
JP6
JP5
7.2Ah
2 x
7.2Ah
3 x
7.2Ah
4 x
7.2Ah
38Ah
65Ah
e)
JP11 when selected open inhibits the battery test regime.
Note: JP11 is always set closed.
f)
J4ĆJ5ĆJ6 set the automatic battery test interval
Link
J4
J5
J6
Time
12 Hours
24 Hours
48 Hours