Service Manual
Chapter 3 - Commissioning
Validating the Installation
3 - 3
3x3 UPS Commissioning
Issue 2 - November 2001
3.3.3 - Auxiliary DC-DC PSU Converter PCB CS0070 Settings
No link setting are required.
3.3.4 - Battery Charger PCB CS0074 Setting
Set the correct battery current limit according to the following link chart.
Link/Ampere
1Amp
3Amps
5Amps
JP1
Open
Open
Closed
JP2
Open
Closed
Open
We recommed to used the following battery current limint setting:
Battery size
7.5 Ah
2x7.5Ah
3x7.5Ah
4x7.5Ah
Battery current
1Amp
1Amp
3Amps
3Amps
Link
Position
Function
Open
Boost recharge disable
JP3
Closed
Boost recharge enable
Open
Battery charger temperature compensation disable
JP4
Closed
Battery charger temperature compensation enable
Battery test settings
Links JP5 to JP10 set the capacity of the standard battery, check the battery Ah to set the corĆ
rect value as shown in the table below
Link
JP10
JP9
JP8
JP7
JP6
JP5
Ah
7.2Ah
2x7.2Ah
3x7.2Ah
4x7.2Ah
38Ah
65Ah
JP11 SHOULD BE ALWAYS CLOSED
Set the automatic battery test interval referring to the table below (it is recommanded to use
48h)
Link
J4
J5
J6
Time
12Hours
24Hours
48Hours
3.3.5 - LCD Display Monitor Board CS0077 Settings
Used for PCB testing porposes only.
Link
Position
Funktion
JP1
1–2
close for normal operation.
JP3
2–3
close for normal operation.
Note: THE SILKSCREEN IDENT (JP1/JPS) IS NEXT TO PIN NUMBER 3.
LINK JP2 ( External EPO ):
JP2 is used to enable the operation of the optional external EPO.
Link
Ext EPO fitted
Ext EPO not fitted
JP2
Open
Close