07: Battery total AH setting
Interface
Setting
Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.
08:
EPO logic setting
Interface
Setting
Set up the EPO function control logic.
AO:
Active Open. When AO is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in open status.
(Default
setting
)
AC:
Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
00: Exit setting
Interface
Setting
Exit the setting mode
Steps for setting programmable outlet ( White Coloured Outlets )
Step 1:
Before entering setting mode, the UPS should be in Stand-by
mode (off-charging) and make sure the battery is connected.
The LCD display is shown as right.
Step 2:
Press and hold the “Selection” button for 5 seconds to enter
Setting mode.
Step 3:
Press the “Up“ button (ON/MUTE) to switch to "02" of program
list. Then press “Enter“ button to enter value setting of
parameter 2. Press the “Up” button to change the value to
“ENA” to enable the programmable outlet function. Then press
“Enter” button again to confirm the setting.