A. Control Panel
NOTE: Total power drawn from all receptacles must not
exceed the nameplate ratings.
B. 120 V, 20 Ampere Duplex Receptacle
20 amps of current may be drawn from either of the
duplex receptacles. However, total power drawn must be kept
within nameplate ratings. These receptacles may be used along
with the twistlock receptacle provided the generator is not
overloaded.
C. 120/240 V, 30 Ampere Twistlock Receptacle
Maximum full load current may be drawn from the
120/240 volt receptacle, provided it is the only receptacle
used. Total current must be limited to the nameplate rating. If
the 120/240 volt receptacle is used along with the 120 volt
receptacle, the total load drawn must not exceed the nameplate
ratings.
D. Circuit Protectors
The receptacles are protected by an AC circuit protector.
If the generator is overloaded or an external short circuit
occurs, the circuit protector will trip. If this occurs,
disconnect all electrical loads and try to determine the cause
of the problem before attempting to use the generator again. If
overloading causes the circuit protector to trip, reduce the
load.
NOTE: Continuous tripping of the circuit protector
may cause damage to generator or equipment.
The circuit
protector may be reset by pushing the button of the protector.
E. Engine On/Off Switch
F. 10 HP OHV Engine
G. Recoil Starter
H. Engine Choke Lever
I.
Oil Filler Cap
J. Oil Drain Plug
K. 7 Gallon Metal Fuel Tank
L. Fuel Tank Cap
M. Fuel Gauge
N. Fuel Shut-Off
O. CordKeeper™ Restraint
The CordKeeper™ restraint is a unique feature used to
prevent plugs from being pulled out of the 120-volt recepta-
cles.
7
English
Customer Hotline 1-800-445-1805
GENERATOR FEATURES
A
B
C
D
F
H
L
J
I
K
M
G
N
D
E
O