background image

 

ELECTRICAL CONNECTIONS

 

 

WARNING: DO NOT APPLY POWER UNTIL TOLD TO DO SO! 

RISK OF SHOCK OR INJURY MAY RESULT.

 Before connecting the 

operator, use a voltmeter to determine that the electrical service is 115 
VAC. This operator cannot be connected to 220 volts. Damage will result, 
which is NOT covered by warranty.  
 
1. 

 Be sure power switches at source and operator are OFF. 

2.Connect incoming power lines and ground wire as follows: 
      

Hot leg (black) to black; Neutral (white) to white; Ground to screw.

 

Note: 

Wiring to operator must use watertight materials in accordance with 

local electric code. 
 

Note: 

Master/Slave installation should have SEPARATE 

power supply wiring. If sharing a power supply line, 
obstruction sensing adjustments may require recalibration. 
 

FOR MASTER/SLAVE INSTALLATION:

 

Note:

 A single unit is considered Master. 

1.  Place jumper on the master operator's P.C. board in the 

"OFF" position (See Fig. 8). 

2.  Place jumper on slave operator's P.C. board in the 

"ON" position. (See Fig. 8).  

3.  Connect terminal # 15 of Master unit to terminal #5 of slave unit.  
4.  Connect terminal # 16 of Master unit to terminal #6 of slave unit.  
5.  Connect Terminal # 17 of Master unit to terminal #7 of slave 

unit. Note: In Master/Slave installation, one unit must be 
converted to LEFT HAND operation. 
 

CONNECTION OF A THREE BUTTON STATION:

 

Note: All control contacts must be NORMALLY OPEN. 
Connect "STOP" button to terminal #4 
Connect "COMMON" button to terminal #5 
Connect "OPEN" button to terminal #6 
Connect "CLOSE" to terminal #7 

 
PRIMARY OBSTRUCTION SENSING DEVICE:

 

Note: 

Gate must move smoothly and easily in manual operation before 

attempting this adjustment. This unit is supplied with a current sensing 
system which will stop gate when activated and then back the gate off 
approximately 2 inches and stop. If the gate is started again and the sensing 
system is activated a second time before hitting a limit switch, the gate will 
stop and sound a warning signal. A constant pressure control will then be 
needed to start the gate. This sensing system has adjustments located on 
printed circuit board (See Fig. 9). The force required to activate the system 
may be adjusted in both OPEN and CLOSE direction separately. Start at 
minimum force, and increase force until it is just over what is required to 
move the gate smoothly without any nuisance tripping. 

NEVER INCREASE FORCE SETTING TO MAKE UP FOR A GATE 
THAT IS NOT MAINTAINED PROPERLY. THIS WILL 
DESENSITIZE THE OPERATION OF THE SAFETY SYSTEM. 

HIGH VOLTAGE 

WIRE GAUGE/ 

DISTANCE CHART 

 

16 AWG 

Up to 200’ 

14 AWG 

200’ to 500’ 

12 AWG 

500’ to 900’ 

10 AWG 

900’ to 1200’ 

 

Over 1200’ consult the factory 

 

HIGH VOLTAGE WIRE GAUGE/ 

DISTANCE CHART 

24 AWG 

Up to 150’ 

20 AWG 

150’ to 250’ 

18 AWG 

500’ to 900’ 

Control wiring should be run as twisted pairs. Do not run 

control  wires in the same conduit as power wires, 

telephone wires or loop detectors leads 

Summary of Contents for RSG 2000

Page 1: ...herewith X Class II Commercial General Access Vehicular Gate Operator A vehicular gate operator or system intended for use in a commercial location or building such as a multifamily housing unit five...

Page 2: ...er to ensure that the total system is safe for its intended use All secondary entrapment safety devices must be U L recognized to complete the operating system SYSTEM DESIGNER SAFETY INSTRUCTIONS 1 Fa...

Page 3: ...the automatic controls do not work Locate the push button or key switch and small warning placard within sight of gate in a secured area at least 10 feet or more from the gate and fence to keep users...

Page 4: ...e sure roller guards have been purchased and installed 7 Your gate system is required to have a primary and a secondary entrapment safety system installed and maintained See page 7 8 8 If your gate cl...

Page 5: ...caught between the grille and the fence post or fence The potential hazard must be guarded It can be simply done by placing a screen mesh on the gate and fence in the area of the gate The screen must...

Page 6: ...d cementing of mounting posts minimum of 2 deep 3 Set mounting posts and electrical conduits in place 4 Pour cement to secure mounting posts and let cure for two days prior to operator installation No...

Page 7: ...ocket See Figs 3 6 8 Pull drive chain though to opposite end of gate cut to correct length and secure to gate bracket using 3 8 inch chain take up bolt as done in steps 4 and 5 Note When pulling drive...

Page 8: ...ntacts must be NORMALLY OPEN Connect STOP button to terminal 4 Connect COMMON button to terminal 5 Connect OPEN button to terminal 6 Connect CLOSE to terminal 7 PRIMARY OBSTRUCTION SENSING DEVICE Note...

Page 9: ...te Install photoelectric cell as close to inside of gate as possible Note Photo cells should be installed across gate opening and behind gate See Fig 11 at least 10 inches above ground 1 After sensors...

Page 10: ...adio s installation manual to determine which wires are for the normally open contacts and which require the 24 VAC power supply TIMER TO CLOSE The operator is equipped with a timer to close option fo...

Page 11: ...wrong turn off main power and recheck drive chain installation See Fig 4 6 If drive chain is correct consult the factory WARNING UNDER NO CIRCUMSTANCES SHOULD CONTROL STATION WIRING BE ALTERED IF ROTA...

Page 12: ...ENTRY Open only 1 Connect MO to terminal 3 2 Connect common to terminal 5 DO NOT Connect N O to terminal 6 FIG 6 EXIT LOOP Open only 1 Connect common yellow to terminal 3 2 Connect N O blue to termina...

Page 13: ...13...

Reviews: