Powerex OL 1K RM User Manual Download Page 3

1. Important Safety Warning 

 
Please comply  with all warnings and operating instructions in  this manual strictly.  Save this 
manual properly and read carefully the following instructions before installing the unit. Do not 
operate  this  unit  before  reading  through  all  safety  information  and  operating  instructions 
carefully 
 

1.1. Transportation 

 

Please  transport  the  UPS  system  only  in  the  original  package  to  protect  against 
shock and impact. 

 

1.2. Preparation 

 

Condensation  may  occur  if  the  UPS  system  is  moved  directly  from  cold  to  warm 
environment. The UPS system must be absolutely dry before being installed. Please 
allow at least two hours for the UPS system to acclimate the environment.   

 

Do not install the UPS system near water or in moist environments. 

 

Do not install the UPS system where it would be exposed to direct sunlight or near 
heater. 

 

Do not block ventilation holes in the UPS housing. 

 

1.3. Installation 

 

Do  not  connect appliances or devices  which  would  overload the UPS system (e.g. 
laser printers) to the UPS output sockets.   

 

Place cables in such a way that no one can step on or trip over them.   

 

Do not connect domestic appliances such as hair dryers to UPS output sockets.   

 

The UPS can be operated by any individuals with no previous experience.   

 

Connect the UPS system only to an earthed shockproof outlet which must be easily 
accessible and close to the UPS system.   

 

Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your 
computer)  to  connect  the  UPS  system  to  the  building  wiring  outlet  (shockproof 
outlet).   

 

Please use only VDE-tested,  CE-marked power cables  to connect the loads to the 
UPS system.   

 

When installing the equipment, it should ensure that the sum of the leakage current 
of the UPS and the connected devices does not exceed 3.5mA. 

 

1.4. Operation 

 

Do not disconnect the mains cable on the UPS system or the building wiring outlet 
(shockproof  socket  outlet)  during  operations  since  this  would  cancel  the  protective 
earthing of the UPS system and of all connected loads.   

 

The  UPS  system  features  its  own,  internal  current  source  (batteries).  The  UPS 
output  sockets  or  output  terminals  block  may  be  electrically  live  even  if  the  UPS 
system is not connected to the building wiring outlet.   

 

In  order  to  fully  disconnect  the  UPS  system,  first  press  the  OFF/Enter  button  to 
disconnect the mains.   

 

Prevent no fluids or other foreign objects from inside of the UPS system.   

 

Summary of Contents for OL 1K RM

Page 1: ...Uninterruptible Power Supply System Powerex OL 1K 2K 3K RM Online UPS Rack USER MANUAL GB...

Page 2: ...view 4 2 2 Rack mounted the UPS 4 2 3 Setup the UPS 5 2 4 Battery replacement 7 2 5 Battery kit assembly option 8 3 Operations 10 3 1 Button operation 10 3 2 LCD Panel 10 3 3 Audible Alarm 12 3 4 LCD...

Page 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...ong run 2K 2K L 3K 3K L 2 1 Rear panel view 1K L 2K L 3K L 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breake...

Page 6: ...uit breaker 40A between the mains and AC input in 3K model for safety operation Step 3 UPS output connection For socket type outputs there two kinds of outputs programmable outlets and general outlets...

Page 7: ...econds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 8 Install sof...

Page 8: ...rnings cautions and notes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull...

Page 9: ...de of UPS Please select correct battery kit procedure below to assemble it 2 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled...

Page 10: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3...

Page 11: ...will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting...

Page 12: ...l by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mo...

Page 13: ...reviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter EP EPO FA Fan TP Temperature CH Charger 3 5 UPS Setting There are three paramete...

Page 14: ...ency on battery mode BAT 50 present output frequency is 50Hz BAT 60 present output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 present output fre...

Page 15: ...int in parameter 3 from 170Vac to 220Vac For 100 110 115 120 127 VAC models 85 115 setting the low voltage point in parameter 3 from 85Vac to 115Vac 08 Programmable outlets enable disable Interface Se...

Page 16: ...er mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input vol...

Page 17: ...temperature 41 x Inverter voltage high 12 x Over load 43 3 8 Warning indicator Warning Icon flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not connec...

Page 18: ...cted Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault...

Page 19: ...he problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery The icon and the warning code flashing on LCD display and alarm is sounding every second Fan i...

Page 20: ...Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 86 88 Battery Mode 83 85 BATTERY Standard Model Battery Type 12 V 9 AH 12 V 9 AH 12 V 9 AH Numbers 2 4 6 Recharge Ti...

Page 21: ...Powerex OL 1K 2K 3K RM Online UPS Rack RU...

Page 22: ...1 1 2 1 1 2 1 2 2 1 3 2 1 4 2 1 5 3 2 4 2 1 4 2 2 4 2 3 5 2 4 7 2 5 8 3 10 3 1 10 3 2 10 3 3 12 3 4 12 3 5 12 3 6 15 3 7 15 3 8 16 4 17 5 18 6 19...

Page 23: ...2 1 1 1 1 2 1 3 VDE CE VDE CE 3 5 1 4 OFF Enter...

Page 24: ...3 1 5...

Page 25: ...4 2 1K 1K L 2K 2K L 3K 3K L 2 1 1K L 2K L 3K L 1 2 3 4 5 6 7 USB 8 RS 232 9 SNMP 10 L 2 2 19 1 2...

Page 26: ...5 2 3 1 1 2 3 2 UPS 3 208 220 230 240 110 115 120 127 NEMA 5 15P 1K 1K L NEMA 5 20P 2K 2K L 3 UPS a b AWG14 2 1 2 AWG12 10 3 3 2 5 3 2 NEMA c d 4 USB RS 232...

Page 27: ...6 USB RS 232 SNMP AS400 SNMP AS400 USB RS 232 5 IN OUT 6 EPO 1 2 1 2 7 ON Mute 8 CD ROM 1 http www power software download com 2 ViewPower 3 4...

Page 28: ...7 9 2 4 1 2 3 4 5 7...

Page 29: ...8 8 2 5 2 1 2 3 4...

Page 30: ...9 4 1 2 3 4 6 1 2 3 4...

Page 31: ...10...

Page 32: ...11 3 3 1 ON Mute ON Mute 2 5 ON Mute 5 OFF Enter 2 Select 10 5 ON Mute Select ON Mute Select 5 3 2...

Page 33: ...12 H M S I 3 5 0 25 26 50 51 75 76 100 0 25 26 50 51 75 76 100...

Page 34: ...13 3 3 4 10 3 4 ENA DIS ESC HLS LLS BAT CF EP EPO FA TP CH 3 5 1 10 2 3 1 2 3...

Page 35: ...08 208 220 220 230 230 240 240 100 110 150 120 127 100 100 110 110 115 115 120 120 127 127 02 2 3 CF ENA CF DIS 03 2 3 BAT 50 50 BAT 60 60 CF 50 50 CF 60 60 04 3 ENA DIS 05 2 3 HLS 2 200 208 220 230 2...

Page 36: ...100 110 115 120 127 3 3 12 06 3 ENA DIS 07 2 3 HLS 200 208 220 230 240 230 264 3 230 264 100 110 115 120 127 120 132 3 120 132 LLS 200 208 220 230 240 170 220 3 170 220 100 110 115 120 127 85 115 3 8...

Page 37: ...16 10 3 0 999 0 999 0 0 10 999 999 00 3 6 40 70 50 60 4 10...

Page 38: ...17 3 7 01 x 13 x 02 x 14 03 x 27 04 x 28 11 x 41 x 12 x 43 3 8 EPO...

Page 39: ...18 4 180 27 28 43...

Page 40: ...19 14 1 2 3 4 11 12 13 41 1 2 5 5 3 5 25 C 5 25 C 40 C 3 1 2 40 C 45 C 2 1 2...

Page 41: ...30 100 120 200 208 220 230 240 100 110 115 120 127 1 48 52 58 62 50 0 2 60 0 2 3 1 2 8 4 85 88 83 85 12 9 12 9 12 9 2 4 6 90 4 1 0 A 27 4 1 41 0 1 82 1 1 8 0 A 27 4 1 41 0 1 82 1 1 x x 380 x 438 x 88...

Reviews: