13
01: Output voltage setting
Interface
Setting
Parameter 3: Output voltage
For 200/208/220/230/240 VAC models, you may choose the
following output voltage:
200:
present output voltage is 200Vac
208:
present output voltage is 208Vac
220:
present output voltage is 220Vac
230:
present output voltage is 230Vac
240:
present output voltage is 240Vac
For 100/110/150/120/127 VAC models, you may choose the
following output voltage:
100:
present output voltage is 100Vac
110:
present output voltage is 110Vac
115:
present output voltage is 115Vac
120:
present output voltage is 120Vac
127:
present output voltage is 127Vac
02: Frequency Converter enable/disable
Interface
Setting
Parameter 2 & 3:
Enable or disable converter mode. You may
choose the following two options:
CF ENA:
converter mode enable
CF DIS:
converter mode disable
03: Output frequency setting
Interface
Setting
Parameter 2 & 3: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50:
present output frequency is 50Hz
BAT 60:
present output frequency is 60Hz
If converter mode is enabled, you may choose the following output
frequency:
CF 50:
present output frequency is 50Hz
CF 60:
present output frequency is 60Hz
04: ECO enable/disable
Interface
Setting
Parameter 3:
Enable or disable ECO function. You may choose
the following two options:
ENA:
ECO mode enable
DIS:
ECO mode disable
05: ECO voltage range setting
Interface
Setting
Parameter 2 & 3:
Set the acceptable high voltage point and low
voltage point for ECO mode by pressing Down key or Up key.
HLS:
High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
For 100/110/115/120/127 VAC models, the setting range in
parameter 3 is from +3V to +12V of the nominal voltage.
LLS:
Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage.
For 100/110/115/120/127 VAC models, the setting voltage in
parameter 3 is from -3V to -12V of the nominal voltage.
Summary of Contents for OL 1K RM
Page 1: ...Uninterruptible Power Supply System Powerex OL 1K 2K 3K RM Online UPS Rack USER MANUAL GB...
Page 21: ...Powerex OL 1K 2K 3K RM Online UPS Rack RU...
Page 23: ...2 1 1 1 1 2 1 3 VDE CE VDE CE 3 5 1 4 OFF Enter...
Page 24: ...3 1 5...
Page 28: ...7 9 2 4 1 2 3 4 5 7...
Page 29: ...8 8 2 5 2 1 2 3 4...
Page 30: ...9 4 1 2 3 4 6 1 2 3 4...
Page 31: ...10...
Page 33: ...12 H M S I 3 5 0 25 26 50 51 75 76 100 0 25 26 50 51 75 76 100...
Page 34: ...13 3 3 4 10 3 4 ENA DIS ESC HLS LLS BAT CF EP EPO FA TP CH 3 5 1 10 2 3 1 2 3...