6. Specifications 

 

MODEL 

OL 100 RM 

OL 2000 RM 

OL 3000 RM 

CAPACITY* 

1000 VA / 800 W 

2000 VA / 1600 W 

3000 VA / 2400 W 

INPUT 

Voltage 
Range 

Low Line Transfer 

80VAC/70VAC/60VAC/50VAC ± 5% or 160VAC/140VAC/120VAC/110VAC ± 5%   

( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)   

Low Line Comeback 

85VAC/75VAC/65VAC/55VAC ± 5 % or 170VAC/150VAC/130VAC/120VAC± 5 %   

High Line Transfer 

150 VAC ± 5 % or 300 VAC ± 5 % 

High Line Comeback 

145 VAC ± 5 % or 290 VAC ± 5 % 

Frequency Range 

45Hz ~ 55 Hz or 56Hz ~ 65 Hz 

Phase 

Single phase with ground 

Power Factor 

 0.99 @ 220-230 VAC or 110-120 VAC 

OUTPUT 

Output voltage 

100/110/115/120/127 VAC or 200/208/220/230/240VAC 

AC Voltage Regulation   

± 1% (Batt. Mode) 

Frequency Range   
(Synchronized Range) 

48 ~ 52 Hz or 58 ~ 62 Hz 

Frequency Range (Batt. Mode) 

50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz 

Current Crest Ratio 

3:1 

Harmonic Distortion 

 2%    (Linear load)   

  8% max (Bat mode before shut down) 

Transfer 
Time 

AC Mode to Batt. Mode 

Zero 

Inverter to Bypass 

4 ms (Typical) 

Waveform (Batt. Mode) 

Pure Sinewave 

EFFICIENCY 

AC Mode 

86 % 

88 % 

Battery Mode 

83 % 

85 % 

BATTERY 

Standard 
Model 

Battery Type 

12 V / 9 AH 

12 V / 9 AH 

12 V / 9 AH 

Numbers 

Recharge Time 

4 hours recover to 90% capacity (Typical) 

Charging Current   

1.0 A(max.) 

Charging Voltage   

27.4 VDC± 1% 

54.8VDC ± 1% 

82.1VDC ± 1% 

Long-run 
Model 

Battery Type & 
Numbers 

Depending on the capacity of external batteries 

Charging Current   

8.0 A(max.) 

Charging Voltage 

27.4 VDC± 1% 

54.8VDC ± 1% 

82.1VDC ± 1% 

PHYSICAL 

Standard 
Model 

Dimension, D X W X H 
mm   

380 x 438 x 88   

480 x 438 x 88 

600 x 438 x 88 

Net Weight (kgs) 

13.2 

20.6 

29 

Long-run 
Model 

Dimension, D X W X H 
mm   

380 x 438 x 88 

480 x 438 x 88 

600 x 438 x 88 

Net Weight (kgs) 

9.1 

11.3 

14.8 

ENVIRONMENT 

Operation Humidity 

20-90 % RH @ 0- 40°C (non-condensing) 

Noise Level 

Less than 50dBA @ 1 Meter 

MANAGEMENT 

Smart RS-232 or USB 

Supports Windows® 2000/2003/XP/Vista/2008/7, Linux, Unix and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 
208VAC. 

 

Summary of Contents for OL 1K RM

Page 1: ...Uninterruptible Power Supply System Powerex OL 1K 2K 3K RM Online UPS Rack USER MANUAL GB...

Page 2: ...view 4 2 2 Rack mounted the UPS 4 2 3 Setup the UPS 5 2 4 Battery replacement 7 2 5 Battery kit assembly option 8 3 Operations 10 3 1 Button operation 10 3 2 LCD Panel 10 3 3 Audible Alarm 12 3 4 LCD...

Page 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...ong run 2K 2K L 3K 3K L 2 1 Rear panel view 1K L 2K L 3K L 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breake...

Page 6: ...uit breaker 40A between the mains and AC input in 3K model for safety operation Step 3 UPS output connection For socket type outputs there two kinds of outputs programmable outlets and general outlets...

Page 7: ...econds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 8 Install sof...

Page 8: ...rnings cautions and notes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull...

Page 9: ...de of UPS Please select correct battery kit procedure below to assemble it 2 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled...

Page 10: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3...

Page 11: ...will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting...

Page 12: ...l by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mo...

Page 13: ...reviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter EP EPO FA Fan TP Temperature CH Charger 3 5 UPS Setting There are three paramete...

Page 14: ...ency on battery mode BAT 50 present output frequency is 50Hz BAT 60 present output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 present output fre...

Page 15: ...int in parameter 3 from 170Vac to 220Vac For 100 110 115 120 127 VAC models 85 115 setting the low voltage point in parameter 3 from 85Vac to 115Vac 08 Programmable outlets enable disable Interface Se...

Page 16: ...er mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input vol...

Page 17: ...temperature 41 x Inverter voltage high 12 x Over load 43 3 8 Warning indicator Warning Icon flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not connec...

Page 18: ...cted Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault...

Page 19: ...he problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery The icon and the warning code flashing on LCD display and alarm is sounding every second Fan i...

Page 20: ...Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 86 88 Battery Mode 83 85 BATTERY Standard Model Battery Type 12 V 9 AH 12 V 9 AH 12 V 9 AH Numbers 2 4 6 Recharge Ti...

Page 21: ...Powerex OL 1K 2K 3K RM Online UPS Rack RU...

Page 22: ...1 1 2 1 1 2 1 2 2 1 3 2 1 4 2 1 5 3 2 4 2 1 4 2 2 4 2 3 5 2 4 7 2 5 8 3 10 3 1 10 3 2 10 3 3 12 3 4 12 3 5 12 3 6 15 3 7 15 3 8 16 4 17 5 18 6 19...

Page 23: ...2 1 1 1 1 2 1 3 VDE CE VDE CE 3 5 1 4 OFF Enter...

Page 24: ...3 1 5...

Page 25: ...4 2 1K 1K L 2K 2K L 3K 3K L 2 1 1K L 2K L 3K L 1 2 3 4 5 6 7 USB 8 RS 232 9 SNMP 10 L 2 2 19 1 2...

Page 26: ...5 2 3 1 1 2 3 2 UPS 3 208 220 230 240 110 115 120 127 NEMA 5 15P 1K 1K L NEMA 5 20P 2K 2K L 3 UPS a b AWG14 2 1 2 AWG12 10 3 3 2 5 3 2 NEMA c d 4 USB RS 232...

Page 27: ...6 USB RS 232 SNMP AS400 SNMP AS400 USB RS 232 5 IN OUT 6 EPO 1 2 1 2 7 ON Mute 8 CD ROM 1 http www power software download com 2 ViewPower 3 4...

Page 28: ...7 9 2 4 1 2 3 4 5 7...

Page 29: ...8 8 2 5 2 1 2 3 4...

Page 30: ...9 4 1 2 3 4 6 1 2 3 4...

Page 31: ...10...

Page 32: ...11 3 3 1 ON Mute ON Mute 2 5 ON Mute 5 OFF Enter 2 Select 10 5 ON Mute Select ON Mute Select 5 3 2...

Page 33: ...12 H M S I 3 5 0 25 26 50 51 75 76 100 0 25 26 50 51 75 76 100...

Page 34: ...13 3 3 4 10 3 4 ENA DIS ESC HLS LLS BAT CF EP EPO FA TP CH 3 5 1 10 2 3 1 2 3...

Page 35: ...08 208 220 220 230 230 240 240 100 110 150 120 127 100 100 110 110 115 115 120 120 127 127 02 2 3 CF ENA CF DIS 03 2 3 BAT 50 50 BAT 60 60 CF 50 50 CF 60 60 04 3 ENA DIS 05 2 3 HLS 2 200 208 220 230 2...

Page 36: ...100 110 115 120 127 3 3 12 06 3 ENA DIS 07 2 3 HLS 200 208 220 230 240 230 264 3 230 264 100 110 115 120 127 120 132 3 120 132 LLS 200 208 220 230 240 170 220 3 170 220 100 110 115 120 127 85 115 3 8...

Page 37: ...16 10 3 0 999 0 999 0 0 10 999 999 00 3 6 40 70 50 60 4 10...

Page 38: ...17 3 7 01 x 13 x 02 x 14 03 x 27 04 x 28 11 x 41 x 12 x 43 3 8 EPO...

Page 39: ...18 4 180 27 28 43...

Page 40: ...19 14 1 2 3 4 11 12 13 41 1 2 5 5 3 5 25 C 5 25 C 40 C 3 1 2 40 C 45 C 2 1 2...

Page 41: ...30 100 120 200 208 220 230 240 100 110 115 120 127 1 48 52 58 62 50 0 2 60 0 2 3 1 2 8 4 85 88 83 85 12 9 12 9 12 9 2 4 6 90 4 1 0 A 27 4 1 41 0 1 82 1 1 8 0 A 27 4 1 41 0 1 82 1 1 x x 380 x 438 x 88...

Reviews: