Powerex OL 1K RM User Manual Download Page 18

17 

 

4. Troubleshooting 

 

If the UPS system does not operate correctly, please solve the problem by using the table 
below.   

 

Symptom 

Possible cause 

Remedy 

No  indication  and  alarm  even 
though the mains is normal.   

The AC input power is not 
connected well. 

Check  if  input  power  cord 
firmly  connected  to  the 
mains.   

The AC input is connected 
to the UPS output. 

Plug  AC  input  power  cord 
to AC input correctly.   

The  icon 

and  the  warning 

code 

  flashing  on  LCD 

display  and  alarm  is  sounding 
every second. 

EPO function is activated. 

Set  the  circuit  in  closed 
position  to  disable  EPO 
function. 

The icon 

and 

  flashing on 

LCD 

display 

and 

alarm 

is 

sounding every second. 

Line 

and 

neutral 

conductors  of  UPS  input 
are reversed. 

Rotate 

mains 

power 

socket  by  180°  and  then 
connect to UPS system. 

The  icon 

and 

  flashing 

on  LCD  display  and  alarm  is 
sounding every second. 

The  external  or  internal 
battery 

is 

incorrectly 

connected. 

Check  if  all  batteries  are 
connected well. 

Fault  code  is  shown  as  27  and 

the  icon 

  is  lighting  on 

LCD 

display 

and 

alarm 

is 

continuously sounding. 

Battery voltage is too high 
or the charger is fault. 

Contact your dealer. 

Fault  code  is  shown  as  28  and 

the  icon 

  is  lighting  on 

LCD 

display 

and 

alarm 

is 

continuously sounding. 

Battery  voltage  is  too  low 
or the charger is fault. 

Contact your dealer. 

The  icon 

  and

is 

flashing  on  LCD  display  and 
alarm  is  sounding  twice  every 
second. 

UPS is overload   

Remove 

excess 

loads 

from UPS output. 

UPS 

is 

overloaded. 

Devices  connected  to  the 
UPS are fed directly by the 
electrical  network  via  the 
Bypass. 

Remove 

excess 

loads 

from UPS output. 

After  repetitive  overloads, 
the  UPS  is  locked  in  the 
Bypass  mode.  Connected 
devices are fed directly by 
the mains. 

Remove 

excess 

loads 

from  UPS  output  first. 
Then  shut  down  the  UPS 
and restart it. 

Fault  code  is  shown  as  43  and 

The  icon 

  is  lighting  on 

LCD 

display 

and 

alarm 

is 

continuously sounding. 

The 

UPS 

shut 

down 

automatically  because  of 
overload 

at 

the 

UPS 

output. 

Remove 

excess 

loads 

from  UPS  output  and 
restart it. 

Summary of Contents for OL 1K RM

Page 1: ...Uninterruptible Power Supply System Powerex OL 1K 2K 3K RM Online UPS Rack USER MANUAL GB...

Page 2: ...view 4 2 2 Rack mounted the UPS 4 2 3 Setup the UPS 5 2 4 Battery replacement 7 2 5 Battery kit assembly option 8 3 Operations 10 3 1 Button operation 10 3 2 LCD Panel 10 3 3 Audible Alarm 12 3 4 LCD...

Page 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Page 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Page 5: ...ong run 2K 2K L 3K 3K L 2 1 Rear panel view 1K L 2K L 3K L 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Input circuit breake...

Page 6: ...uit breaker 40A between the mains and AC input in 3K model for safety operation Step 3 UPS output connection For socket type outputs there two kinds of outputs programmable outlets and general outlets...

Page 7: ...econds to power on the UPS Note The battery charges fully during the first five hours of normal operation Do not expect full battery run capability during this initial charge period Step 8 Install sof...

Page 8: ...rnings cautions and notes before replacing batteries Note Upon battery disconnection equipment is not protected from power outages Step 1 Step 2 Step 3 Remove front panel Disconnect battery wires Pull...

Page 9: ...de of UPS Please select correct battery kit procedure below to assemble it 2 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled...

Page 10: ...4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3...

Page 11: ...will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting...

Page 12: ...l by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Programmable outlets information Indicates that programmable management outlets are working Mo...

Page 13: ...reviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter EP EPO FA Fan TP Temperature CH Charger 3 5 UPS Setting There are three paramete...

Page 14: ...ency on battery mode BAT 50 present output frequency is 50Hz BAT 60 present output frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 present output fre...

Page 15: ...int in parameter 3 from 170Vac to 220Vac For 100 110 115 120 127 VAC models 85 115 setting the low voltage point in parameter 3 from 85Vac to 115Vac 08 Programmable outlets enable disable Interface Se...

Page 16: ...er mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input vol...

Page 17: ...temperature 41 x Inverter voltage high 12 x Over load 43 3 8 Warning indicator Warning Icon flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not connec...

Page 18: ...cted Check if all batteries are connected well Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault...

Page 19: ...he problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery The icon and the warning code flashing on LCD display and alarm is sounding every second Fan i...

Page 20: ...Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 86 88 Battery Mode 83 85 BATTERY Standard Model Battery Type 12 V 9 AH 12 V 9 AH 12 V 9 AH Numbers 2 4 6 Recharge Ti...

Page 21: ...Powerex OL 1K 2K 3K RM Online UPS Rack RU...

Page 22: ...1 1 2 1 1 2 1 2 2 1 3 2 1 4 2 1 5 3 2 4 2 1 4 2 2 4 2 3 5 2 4 7 2 5 8 3 10 3 1 10 3 2 10 3 3 12 3 4 12 3 5 12 3 6 15 3 7 15 3 8 16 4 17 5 18 6 19...

Page 23: ...2 1 1 1 1 2 1 3 VDE CE VDE CE 3 5 1 4 OFF Enter...

Page 24: ...3 1 5...

Page 25: ...4 2 1K 1K L 2K 2K L 3K 3K L 2 1 1K L 2K L 3K L 1 2 3 4 5 6 7 USB 8 RS 232 9 SNMP 10 L 2 2 19 1 2...

Page 26: ...5 2 3 1 1 2 3 2 UPS 3 208 220 230 240 110 115 120 127 NEMA 5 15P 1K 1K L NEMA 5 20P 2K 2K L 3 UPS a b AWG14 2 1 2 AWG12 10 3 3 2 5 3 2 NEMA c d 4 USB RS 232...

Page 27: ...6 USB RS 232 SNMP AS400 SNMP AS400 USB RS 232 5 IN OUT 6 EPO 1 2 1 2 7 ON Mute 8 CD ROM 1 http www power software download com 2 ViewPower 3 4...

Page 28: ...7 9 2 4 1 2 3 4 5 7...

Page 29: ...8 8 2 5 2 1 2 3 4...

Page 30: ...9 4 1 2 3 4 6 1 2 3 4...

Page 31: ...10...

Page 32: ...11 3 3 1 ON Mute ON Mute 2 5 ON Mute 5 OFF Enter 2 Select 10 5 ON Mute Select ON Mute Select 5 3 2...

Page 33: ...12 H M S I 3 5 0 25 26 50 51 75 76 100 0 25 26 50 51 75 76 100...

Page 34: ...13 3 3 4 10 3 4 ENA DIS ESC HLS LLS BAT CF EP EPO FA TP CH 3 5 1 10 2 3 1 2 3...

Page 35: ...08 208 220 220 230 230 240 240 100 110 150 120 127 100 100 110 110 115 115 120 120 127 127 02 2 3 CF ENA CF DIS 03 2 3 BAT 50 50 BAT 60 60 CF 50 50 CF 60 60 04 3 ENA DIS 05 2 3 HLS 2 200 208 220 230 2...

Page 36: ...100 110 115 120 127 3 3 12 06 3 ENA DIS 07 2 3 HLS 200 208 220 230 240 230 264 3 230 264 100 110 115 120 127 120 132 3 120 132 LLS 200 208 220 230 240 170 220 3 170 220 100 110 115 120 127 85 115 3 8...

Page 37: ...16 10 3 0 999 0 999 0 0 10 999 999 00 3 6 40 70 50 60 4 10...

Page 38: ...17 3 7 01 x 13 x 02 x 14 03 x 27 04 x 28 11 x 41 x 12 x 43 3 8 EPO...

Page 39: ...18 4 180 27 28 43...

Page 40: ...19 14 1 2 3 4 11 12 13 41 1 2 5 5 3 5 25 C 5 25 C 40 C 3 1 2 40 C 45 C 2 1 2...

Page 41: ...30 100 120 200 208 220 230 240 100 110 115 120 127 1 48 52 58 62 50 0 2 60 0 2 3 1 2 8 4 85 88 83 85 12 9 12 9 12 9 2 4 6 90 4 1 0 A 27 4 1 41 0 1 82 1 1 8 0 A 27 4 1 41 0 1 82 1 1 x x 380 x 438 x 88...

Reviews: