8. Maintenance 

With a minimal amount of maintenance, you can expect the UPS to application, otherwise 
consider changing the batteries. have a long life free of trouble. The most critical issues for 
the reliability of the UPS are environmental issues. Ensure that the temperature and 
humidity are always according to specifications and keep the area around the unit clean and 
dust free. 

At a temperature of 25°C, the typical battery lifetime is 4 years. 

Also check at regular intervals of 6 to 12 months whether the back-up time of the battery is 
adequate for its 

 

WARNING! 

Batteries may cause electrical shock or burn from high short circuit 

currents. Please observe the following precautions: 1. Remove jewelry and metal 

objects such as watches and rings. 2. Use tools that have insulated handles. 3. Keep 

tools and other metal objects from contacting and away from the batteries. 

ELECTRIC ENERGY HAZARD. Do not attempt to rewire, alter, or change any 

battery wiring or connectors. Attempting to make such alterations can cause 

injury. 

Replace the batteries with the same number and type as originally installed 

batteries. 

DO NOT DISCONNECT the batteries while UPS is in Battery mode. 

 

9. Warranty 

Warranty on this product is valid against defects in material and workmanship 

for a period of 24 months from its original date of purchase. 

 

 

25

10. Technical  Specifications 

GENERAL 

Rated power 

5000VA, 6000 VA, 8000 VA, 10000 VA, 12000VA at p.f 0.7 

Technology 

On-line, double conversion topology with automatic bypass 

INPUT 

Phase 

Single phase three wires or three phases five wires 

Bypass Voltage:   

184-265 VAC (user selectable) 

Input Voltage range:   

120/140//160/180 VAC-276 VAC 

Frequency: 

50/60 Hz. Auto selection 

Frequency window from mains 

45-65 Hz 

Synchronization window 

± 3Hz. 

Input current 

5000 VA 19.2A, 6000 VA 23.0A, 8000 VA 30.7A, 10000 VA 38.3A, 

1200VA 46.0A, 8000VA 3/1 17.7A, 10000VA 3/1 22.1A, 12000VA 
3/1 26.5A 

Input Power factor: 

>=0.98 (1

3W), >=0.95 (3

5W) 

OUTPUT 

Output Voltage: 

208/220/230/240 VAC, selectable from LCD panel 

Voltage regulation: 

± 2% 

Voltage distortion: 

< 5% THD at full non-linear load, < 3% THD at full linear load 

Frequency regulation 

± 0.25 Hz (battery or free running mode) 

* 120V at 25% load, 140V at 50%, 160V at 75%, 180V at 100%. 
Dynamic response: 

± 9 % max from 100% to 20 % or from 20% to 100 % linear load 

Overload capacity: 

100-125% 1 min, 125-150% 10 sec 

Efficiency: 

greater than 88% 

 

ENVIRONMENTAL 

Ambient temperature: 

+0 °C to +40 °C 

Recommended temperature: 

+15 °C to +25 °C 

Storage temperature: 

-15 °C to +50 °C 

Cooling: Forced 

air-cooling 

Humidity: 0-95%, 

non-condensing 

Audible noise: 

< 55 db normal and battery mode (5000-6000 VA) 

 

< 65 db normal and battery mode (8000-12000 VA) 

STANDARDS 

Safety:  

EN50091-1-1 

Emissions:  

EN50091-2  

Immunity:  

EN50091-2 

Summary of Contents for 12K VA

Page 1: ...fluenced by harmful interference from the equipment it is recommended to use one of the following preventive measures Place the receiving antenna in a separate location or orientation Ensure a greater...

Page 2: ...servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is not isolated from AC input hazardous voltage may exist between battery terminals...

Page 3: ...nstallation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation and regulations Only qualified personnel should conduct these insta...

Page 4: ...management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of normal mode operation a battery discharge test is performed...

Page 5: ...in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operator 5 4 Storage 4 1 Storage Please adhere to the followi...

Page 6: ...ptions Avoid extremes of temperature and humidity Maximal battery life can be attained with a recommended temperature range of 15 C to 25 C Provide protection for the equipment from moisture Space and...

Page 7: ...8 5K 6KVA Rear panel With ISO 9 8K 12KVA Rear panel Without ISO...

Page 8: ...the installation site has all electrical connections properly carried out In addition refer to figures 2 and 3 to check the fuse and cable dimensions Isolate and secure the source against reclosing Bo...

Page 9: ...ters to select Default settings are as follows Settings Selection Factory default Output Voltage Setting 208 220 230 240 Vac 230V FOR HV series Input Bypass Voltage 10 10 15 15 20 10 15 Input Frequenc...

Page 10: ...RI Output 8 24 VDC Power Fig 5 Caution Max rated values 24Vdc 50mA 15 USB port option Connecting the UPS to your computer is accomplished through the USB port on the back of your computer USB complian...

Page 11: ...Push the ENTER button to confirm and enable your function f If no pressing within 10 seconds it will return to original status 4 ENTER button Use this button to enter enable or confirm the function t...

Page 12: ...CPU Version 19 UPS configurations 1 Various settings that have been chosen are shown in the UPS setting display 2 To enter configuration mode press the FUNC button for one second The first configurati...

Page 13: ...ed For UPS to predict Backup time 0 only internal batteries 1 one external cabinet 2 two external cabinets 0 Site wiring alarm Sit Fault Set You can enable or disable the site wiring alarm Enable Disa...

Page 14: ...ps The UPS is doing a battery test No action needed The UPS will return to normal operation when it successfully completes the battery test Over Charge Constant beep Batteries are overcharged Turn off...

Page 15: ...al and workmanship for a period of 24 months from its original date of purchase 25 10 Technical Specifications GENERAL Rated power 5000VA 6000 VA 8000 VA 10000 VA 12000VA at p f 0 7 Technology On line...

Page 16: ...mber of batteries 20 20 20 20 40 Backup time full load 7 min 6 min 5 min 6 min 6min Recharge time 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 Without ISOTR 280x580x570 280x58...