7.4 Interpreting UPS messages 

Troubleshooting procedures described here give simple instructions in determining UPS 
malfunctions. 

Start the troubleshooting procedure if you witness any alarm indication on the control panel. 

Alarm indicators 

The UPS gives the following audible alarms: 

 

If UPS is on battery and the ON BATTERY LED is on, UPS will beep every 5 seconds. 

 

If the battery capacity is low and the ON BATTERY LED is flashing, the UPS will 
beep twice every 5 seconds. 

 

If UPS is on bypass and the BYPASSED LED is on, UPS will no beep. 

 

If UPS has an internal fault and the ALARM LED is on, the UPS will give a constant 
audible alarm displaying the cause on the LCD display. 

Silencing an alarm 

By pressing any of the three buttons on the front panel, the alarm can be turned off, except 
when the battery is low, which will cause the alarm to resound. 

On the LCD display, you can also choose silent alarm mode which will not warn you of any 
malfunction audibly. 

 

23

7.5 Trouble shooting 

Displayed on LCD 

Audible Alarm Alarm Description 

What You Should Do 

Output Overload 

Two Beeps per 
second 

The UPS is overloaded (in 
Line Mode). Your 
equipment needs more 
power than the UPS can 
provide. The UPS operates 
in bypass. 

Shut off the least important 
equipment connected to the 
UPS. If this solves the 
overload problem, the UPS 
will switch from bypass back 
to normal operation. 

Battery Test 

No Beeps 

The UPS is doing a battery 
test. 

No action needed. The UPS 
will return to normal operation 
when it successfully completes 
the battery test. 

Over-Charge 

Constant beep 

Batteries are 
overcharged. 

Turn off protected loads. Turn 
off UPS and call your local 
dealer 

Low Battery 

2 beeps every 
5seconds 

The unit is operating on 
Battery Power and will shut 
down soon due to very low 
battery voltage 

The unit will restart 
Automatically when 
acceptable power returns. 

On-Battery 

Once every 5 
seconds 

The unit is operating on 
Battery Power. 

Save your data and perform a 
controlled shutdown. 

Charger Failure 

Constant beep 

Charger has failed. 

Phone the local dealer 

Over-Temperature 

Constant beep 

High ambient Temperature. Make sure the unit’s fans and 

vent holes are not blocked, and 
make sure the ambient 
surrounding temperature is not 
above 40 degree C. If these 
conditions did not solve the 
problem, call your service 
representative.  

Output Short 

Constant beep 

Output short circuit 

Call the Local dealer 

High output Voltage 

Constant beep 

High output voltage 

Call the Local dealer 

Low Output Voltage 

Constant beep 

Low output voltage 

Call the Local dealer 

  Bus Fault 

2 Beeps per 
second 

High internal DC bus 
Voltage. 

Turn off protected loads. Turn 
off UPS and call your local 
dealer 

Site wiring Fault 

1 Beep per 
second 

Voltage detected Between 
Neutral and Ground 

UPS mains connector polarity 
Wrong. Rotate the connector 
(Schuko). UPS installed to 
mains supply without ground. 
See page 15 on how to disable 
the Site wiring alarm 

Line abnormal 

1 Beep per 
second 

Wrong AC Line backed up 
during auto restart 

 

Summary of Contents for 12K VA

Page 1: ...fluenced by harmful interference from the equipment it is recommended to use one of the following preventive measures Place the receiving antenna in a separate location or orientation Ensure a greater...

Page 2: ...servicing to qualified service personnel CAUTION Non isolated Battery supply Risk of electric shock battery circuit is not isolated from AC input hazardous voltage may exist between battery terminals...

Page 3: ...nstallation must be carried out in accordance with this manual Electrical installations must also carefully follow local legislation and regulations Only qualified personnel should conduct these insta...

Page 4: ...management system always monitors the conditions of the batteries sends any forewarnings if replacement is needed Otherwise every 30 days of normal mode operation a battery discharge test is performed...

Page 5: ...in this manual The greatest care possible must be taken for any of these operations and any change thereof may prove very hazardous to the operator 5 4 Storage 4 1 Storage Please adhere to the followi...

Page 6: ...ptions Avoid extremes of temperature and humidity Maximal battery life can be attained with a recommended temperature range of 15 C to 25 C Provide protection for the equipment from moisture Space and...

Page 7: ...8 5K 6KVA Rear panel With ISO 9 8K 12KVA Rear panel Without ISO...

Page 8: ...the installation site has all electrical connections properly carried out In addition refer to figures 2 and 3 to check the fuse and cable dimensions Isolate and secure the source against reclosing Bo...

Page 9: ...ters to select Default settings are as follows Settings Selection Factory default Output Voltage Setting 208 220 230 240 Vac 230V FOR HV series Input Bypass Voltage 10 10 15 15 20 10 15 Input Frequenc...

Page 10: ...RI Output 8 24 VDC Power Fig 5 Caution Max rated values 24Vdc 50mA 15 USB port option Connecting the UPS to your computer is accomplished through the USB port on the back of your computer USB complian...

Page 11: ...Push the ENTER button to confirm and enable your function f If no pressing within 10 seconds it will return to original status 4 ENTER button Use this button to enter enable or confirm the function t...

Page 12: ...CPU Version 19 UPS configurations 1 Various settings that have been chosen are shown in the UPS setting display 2 To enter configuration mode press the FUNC button for one second The first configurati...

Page 13: ...ed For UPS to predict Backup time 0 only internal batteries 1 one external cabinet 2 two external cabinets 0 Site wiring alarm Sit Fault Set You can enable or disable the site wiring alarm Enable Disa...

Page 14: ...ps The UPS is doing a battery test No action needed The UPS will return to normal operation when it successfully completes the battery test Over Charge Constant beep Batteries are overcharged Turn off...

Page 15: ...al and workmanship for a period of 24 months from its original date of purchase 25 10 Technical Specifications GENERAL Rated power 5000VA 6000 VA 8000 VA 10000 VA 12000VA at p f 0 7 Technology On line...

Page 16: ...mber of batteries 20 20 20 20 40 Backup time full load 7 min 6 min 5 min 6 min 6min Recharge time 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 8 hours to 90 Without ISOTR 280x580x570 280x58...

Page 17: ...28 MAINTENANCE SWITCH NORMAL BY PASS 1 2 INV MAIN INV MAIN or...