9
07: Acceptable high frequency setting in Bypass/ECO mode
Interface
Setting
Press the Down key or Up key to set
acceptable high frequency point (HLS) in bypass/ECO mode:
For 50Hz output frequency models:
51-55Hz: setting the frequency low loss point from 51Hz to
55HZ (Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: setting the frequency low loss point from 61Hz to
65Hz (Default: 63.0Hz)
08: ECO mode enable/disable
Interface
Setting
ENA: ECO mode enable
DIS: ECO mode disable (Default)
09: Acceptable low voltage setting in ECO mode
Interface
Setting
Press the Down key or Up key to set
acceptable low voltage point (LLS) in ECO mode:
For 200/208/220/230/240 VAC models,
setting range is from -7V to -24V of the nominal voltage.
(Default: -12V)
For 100/110/115/120/127 VAC models,
setting range is from -3V to -12V of the nominal voltage.
(Default: -6V)
10: Acceptable high voltage setting in ECO mode
Interface
Setting
Press the Down key or Up key to set
acceptable high voltage point (HLS) in ECO mode:
For 200/208/220/230/240 VAC models,
setting range is from +7V to +24V of the nominal voltage.
(Default: +12V)
For 100/110/115/120/127 VAC models,
setting range is from +3V to +12V of the nominal voltage.
(Default: +6V)