18
11: Hot standby function enable/disable
l.
Interface
Setting
Parameter 2:
Enable or disable hot standby function.
ENA:
Hot standby function is enabled. It means that the current
UPS is set to host of the hot standby function, and it will restart
after AC recovery even without battery connected.
DIS:
Hot standby function is disabled. The UPS is running at
normal mode and can’t restart without battery
12: Battery voltage calibration
Interface
Setting
Parameter 2:
The voltage range is from -5.7V to 5.7V, the default value is 0V.
13: Charger voltage calibration
Interface
Setting
Parameter 2:
Voltage range is from -9.9V to 9.9V and the default
value is 0V.
NOTE:
Before making voltage adjustment, be sure to disconnect all
batteries first to get the accurate charger voltage.
Strongly suggest using the default value (0).
Any modification should be suitable to battery specifications.
14: Maximum charger current setting
Interface
Setting
Parameter 2:
The maximum charging current could be adjusted.
Default value is 4A for long run model and 1A for standard model.
The setting range is 0.5A~6A for long run model, and 0.5A~2A for
standard model.
Note:
Any modification should be suitable to battery specifications.
If input voltage is below 200VAC, the ups will reduce charging
current to 4A automatically even though the setting is 6A.