Page
21
of
41
R
EMOTE AND
A
UTO
S
TARTING THE
G
ENERATOR
S
ET
If desired, the generator set is capable of being started either manually from a remote panel or
automatically via an external signal from a transfer switch or other device. The following steps are used
to set up the controller to accept an external start signal. Ensure the Pre-Start checks above have been
completed before putting the generator set into AUTO mode.
WARNING:
Putting the generator set in AUTO
mode may cause the generator set to start without warning.
This can result in severe injury or death.
Use extreme caution when working around the generator set
when it is in AUTO mode.
DO NOT
service the generator set while it is in AUTO mode.
1. Set the Master Power Switch to the ON position. The controller will power on and boot-up to the
last start mode used.
2. Press the AUTO (A) button to put the controller in AUTO mode. The screen will display
Waiting
To Start
.
3. Turn the Main Set AC Circuit Breaker to the ON position.
4. The generator set is now ready to accept an external start signal.
5. Continue to monitor the generator set during operation to ensure it is operating correctly.
M
ANUALLY
S
HUTTING
D
OWN THE
G
ENERATOR
S
ET
The following steps are used to manually shut down the generator set.
1. Turn the Main Set AC Circuit Breaker to the OFF position.
NOTICE:
DO NOT
shut down the generator set under load. Doing so may cause damage to the
generator set. Damage caused by shutting down the generator set under load is not covered under
warranty.
2. Allow the generator set to cool down by letting it run for 2-3 minutes with no load.
3. Press the OFF (O) button to shut down the generator set. The screen will display an
ETS
SHUTDOWN
timer.
4. Once the engine has stopped, set the Master Power Switch to the OFF position.
NOTICE:
DO NOT
shut down the generator set by setting the Master Power Switch to the OFF
position while the engine is running. Doing so may cause damage to the generator set. Damage
caused by shutting down the generator set by setting the Master Power Switch to the OFF position
while the engine is running is not covered under warranty.
WARNING
Accidental start-up.
Can cause severe injury or death.
Summary of Contents for PT-10KSIC
Page 1: ......
Page 13: ...Page 13 of 41 COMPONENT LOCATIONS...
Page 14: ...Page 14 of 41...
Page 15: ...Page 15 of 41...
Page 37: ...Page 37 of 41 120 240 VAC A TYPE GENERATOR END WITH AS440 AVR...
Page 38: ...Page 38 of 41 120VAC ONLY CE TYPE GENERATOR END WITH VR3 1B AVR...
Page 39: ...Page 39 of 41 120 240VAC CE TYPE GENERATOR END WITH VR3 1B AVR...
Page 40: ...Page 40 of 41 CONTROL WIRING WITH PTG350 CONTROLLER...
Page 41: ...Page 41 of 41 Revision Date Initial Release 2 5 2020...