P
RE
-S
TART
To ensure proper and reliable operation, always inspect the generator set daily and prior to each startup.
Verify that the engine oil level is at the correct level. Add if necessary.
Verify that the coolant is at the correct level. Add if necessary.
Check for leaks and/or fluids in the compartment. Clean and/or repair as necessary.
Check fuel level in tank.
Check battery cables and terminals are secure.
Check battery terminals for corrosion.
Check for water in fuel and drain if necessary.
Check the controller for DTC codes or failures.
Verify drive belt tension is correct.
Inspect all hoses and belts for damage or wear. Replace if necessary.
Inspect wiring for damage, fraying, bare spots, and proper connection. Replace if necessary.
Ensure the area around the generator set is free of loose objects and debris.
Verify all guards and covers are in place and securely fastened.
Ensure the Main Set AC Circuit Breaker is in the OFF position.
Ensure the Master Power Switch is in the OFF position.
M
ANUALLY
S
TARTING THE
G
ENERATOR
S
ET
The generator set is capable of being started automatically, remotely and from the local controller on the
genset. The following steps are used to start the generator set manually from the local controller. Ensure
the Pre-Start checks above have been completed before attempting to start the generator set.
1. Set the Master Power Switch to the ON position. The controller will power on and boot-up to the
last start mode used.
2. Press the OFF (O) button to put the controller in MANUAL mode. The screen will display
NOT
IN AUTO START ENABLED
.
3. Press the RUN (I) button to start the generator set. The screen will display a
PREHEATING
count down, a
CRANKING
countdown, and then display
MANUAL RUN..
4. Allow the engine to warm up for 1-2 minutes.
5. Verify that all engine and generator output parameters are nominal.
6. Turn the Main Set AC Circuit Breaker to the ON position to start supplying power.
7. Continue to monitor the generator set during operation to ensure it is operating correctly.
Summary of Contents for PT-10KSIC
Page 1: ......
Page 13: ...Page 13 of 41 COMPONENT LOCATIONS...
Page 14: ...Page 14 of 41...
Page 15: ...Page 15 of 41...
Page 37: ...Page 37 of 41 120 240 VAC A TYPE GENERATOR END WITH AS440 AVR...
Page 38: ...Page 38 of 41 120VAC ONLY CE TYPE GENERATOR END WITH VR3 1B AVR...
Page 39: ...Page 39 of 41 120 240VAC CE TYPE GENERATOR END WITH VR3 1B AVR...
Page 40: ...Page 40 of 41 CONTROL WIRING WITH PTG350 CONTROLLER...
Page 41: ...Page 41 of 41 Revision Date Initial Release 2 5 2020...